SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
HAND Command
External Run
(Terminal, Serial, or
Option)
HAND LED
Drive Operation
HOA Mode
Description
HOA State
Yes
Yes/No
Long Blink
(50% duty)
No
Normal
Output Frequency is 0 or drive
decelerates to STOP
HAND
Yes
Yes/No
Double Blink
No
Normal
Waiting for cycle of commands
Example:
•
Drive Ready condition was
removed
•
Drive starts Fast-Stop operation
HAND
*1
The LED is available when
o2-24 ≠ 2 [LED Light Function Selection ≠ Keypad LED Light Disable]
.
■
S5-01: HAND Frequency Reference Source
No.
(Hex.)
Name
Description
Default
(Range)
S5-01
(322F)
HAND Frequency Reference
Source
Sets the frequency reference source when HAND Mode is active.
1
(0 - 2)
0 : HAND Analog Input
The drive operates as specified by the frequency reference from the MFAI terminal set for
H3-xx = 2E [MFAI
Function Selection = Hand Frequency Ref or Setpoint]
.
1 : HAND Ref S5-05 or PID SP S5-06
The drive operates as specified by the frequency reference set in
S5-05 [HAND Frequency Reference]
or PID setpoint
set in
S5-06 [HAND Setpoint]
.
2 : Set by b1-01
The drive operates as specified by the frequency reference from the source set in
b1-01
.
■
S5-02: HAND/AUTO Switchover During Run
No.
(Hex.)
Name
Description
Default
(Range)
S5-02
(3230)
HAND/AUTO Switchover
During Run
Sets the function to enable or disable switching between HAND and AUTO Mode during run.
1
(0, 1)
0 : Disabled
1 : Enabled
■
S5-03: HAND Mode PID Selection
No.
(Hex.)
Name
Description
Default
(Range)
S5-03
(3231)
RUN
HAND Mode PID Selection
Sets the function to enable or disable PI function when HAND mode is active.
0
(0, 1)
0 : Disabled
1 : Enabled
Note:
If
b5-01 = 0 [PID Mode Setting = Disabled]
, the drive disables Hand Mode PID.
■
S5-05: HAND Frequency Reference
No.
(Hex.)
Name
Description
Default
(Range)
S5-05
(3233)
RUN
HAND Frequency Reference Sets the frequency reference when HAND Mode is active, PID is disabled and
S5-01 = 1 [HAND
Frequency Reference Source = HAND Ref S5-05 or PID SP S5-06]
.
0.00 Hz
(0.00 - 400.00 Hz)
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...