S5: Hand/Off/Auto Operation
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
S5-01
(322F)
HAND Frequency
Reference Source
Sets the frequency reference source when HAND Mode is active.
0 : HAND Analog Input
1 : HAND Ref S5-05 or PID SP S5-06
2 : Set by b1-01
1
(0 - 2)
S5-02
(3230)
HAND/AUTO
Switchover During Run
Sets the function to enable or disable switching between HAND and AUTO Mode during
run.
0 : Disabled
1 : Enabled
1
(0, 1)
S5-03
(3231)
RUN
HAND Mode PID
Selection
Sets the function to enable or disable PI function when HAND mode is active.
0 : Disabled
1 : Enabled
Note:
If
b5-01 = 0 [PID Mode Setting = Disabled]
, the drive disables Hand Mode PID.
0
(0, 1)
S5-05
(3233)
RUN
HAND Frequency
Reference
Sets the frequency reference when HAND Mode is active, PID is disabled and
S5-01 = 1
[HAND Frequency Reference Source = HAND Ref S5-05 or PID SP S5-06]
.
0.00 Hz
(0.00 - 400.00 Hz)
S5-06
(3234)
RUN
HAND Setpoint
Sets the System Setpoint when HAND Mode is active, PID is enabled and
S5-01 = 1
[HAND Frequency Reference Source = HAND Ref S5-05 or PID SP S5-06]
.
Note:
Parameters
b5-46 [PID Unit Display Selection]
,
b5-38 [PID User Unit Display
Scaling]
, and
b5-39 [PID User Unit Display Digits]
set the unit, range, and resolution.
0.0
(0.0 - 6000.0)
S5-07
(3235)
Operation HAND Key
Sets the HAND key on the HOA keypad to let you switch between HAND Mode and
AUTO Mode.
0 : Disabled
1 : Enabled
1
(0, 1)
S5-08
(3D31)
RUN
HAND Reference Prime
Loss Level
Sets the level at which the drive will detect the Loss of Prime in the pump.
Note:
•
If these conditions occur at the same time, the drive will detect
LOP [Loss of Prime]
:
–
The monitor set by
Y1-18 [Prime Loss Detection Method]
≤
S5-08
for longer than
Y1-20 [Prime Loss Time]
–
Output frequency ≥
S5-05 [HAND Frequency Reference]
•
The drive response to the Loss of Prime condition changes when the
Y1-22 [Prime
Loss Selection]
setting changes.
•
Parameter
Y1-18 [Prime Loss Detection Method]
sets the units for this parameter.
0.0
(0.0 - 1000.0)
◆
S6: Protection
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
S6-01
(3236)
Emergency Override
Speed
Sets the speed command for emergency override mode when
S6-02 = 0 [Emergency
Override Ref Selection = Use S6-01 Reference]
.
Note:
Parameter default is lower-limited to
E1-09
. The default setting will automatically
increase when
E1-09
>
S6-01
.
1.50 Hz
(1.50 - 60.00 Hz)
S6-02
(3237)
Emergency Override Ref
Selection
Sets the Emergency Override Speed Source:
0 : Use S6-01 Reference
1 : Use Frequency Reference
2 : System PID Mode
3 : Independent PID Mode
0
(0 - 3)
S6-03
(323A)
EMOVR Independent
PID Scale
Sets the scaling on the Emergency PID Feedback and Setpoint (if programmed) Analog
Inputs.
Note:
•
S6-05 [EMOVR Independent PID Unit Digit]
sets the resolution for this parameter.
•
S6-04 [EMOVR Independent PID Unit]
sets the units for this parameter.
100.00
(0.10 - 600.00)
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...