YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
647
9.14
S: Special Applications
◆
S1: Dynamic Noise Control
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
S1-01
(3200)
Dynamic Noise Control
Sets the function that decreases the output voltage in variable torque applications to
decrease audible noise.
0 : Disabled
1 : Enabled
1
(0, 1)
S1-02
(3201)
Voltage Reduction Rate
Sets the rate at which the drive will decrease the output voltage as a percentage of the V/f
pattern when operating with no load.
50.0%
(50.0 - 100.0%)
S1-03
(3202)
Voltage Restoration Level Sets the level at which the drive will start to restore the voltage as a percentage of the drive
rated torque.
20.0%
(0.0 - 90.0%)
S1-04
(3203)
Voltage Restoration Off
Level
Sets the level at which voltage restoration for the V/f pattern is complete as a percentage of
the drive rated torque. If the output is more than
S1-04
, the drive will control the voltage as
specified by the V/f pattern setting.
Note:
The lower limit of this parameter is the value of
S1-03 [Voltage Restoration Level]
+
10.0%.
50.0%
(10.0 - 100.0%)
S1-05
(3204)
Volt Restore Sensitivity
Time K
Sets the level of sensitivity of the output torque and LPF time constant for the voltage
reduction rate. You can adjust the level of sensitivity with the load response.
1.000 s
(0.000 - 3.000 s)
S1-06
(3205)
Volt Restore Impact Load
Time K
Sets the voltage restoration time constant when you add an impact load.
0.050 s
(0.000 - 1.000 s)
S1-07
(324C)
Output Phase Loss Level
Decreases the output phase loss level when Dynamic Noise control is active.
100.0%
(10.0 - 100.0%)
◆
S2: Sequence Run Timers
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
S2-01
(3206)
Timer 1 Start Time
Sets the start time for timer 1.
Note:
•
Default is when
o4-22 = 1 [Time Format = 12 Hour Clock]
. When
o4-22 = 0 [24
Hour Clock]
, default is 00:00. When
o4-22 = 2 [12 Hour JP Clock]
, default is 00:00
AM.
•
Range is when
o4-22 = 1
. When
o4-22 = 0
, range is 00:00 to 24:00. When
o4-22 =
2
, range is 00:00 AM to 11:59 PM.
12:00
(12:00 AM - 11:59 PM)
S2-02
(3207)
Timer 1 Stop Time
Sets the stop time for timer 1.
Note:
•
Default is when
o4-22 = 1 [Time Format = 12 Hour Clock]
. When
o4-22 = 0 [24
Hour Clock]
, default is 00:00. When
o4-22 = 2 [12 Hour JP Clock]
, default is 00:00
AM.
•
Range is when
o4-22 = 1
. When
o4-22 = 0
, range is 00:00 to 24:00. When
o4-22 =
2
, range is 00:00 AM to 11:59 PM.
12:00
(12:00 AM - 11:59 PM)
S2-03
(3208)
Timer 1 Day Selection
Sets the days for which sequence timer 1 is active.
0 : Timer Disabled
1 : Daily
2 : Mon - Fri
3 : Sat - Sun
4 : Monday
5 : Tuesday
6 : Wednesday
7 : Thursday
8 : Friday
9 : Saturday
10 : Sunday
0
(0 - 10)
S2-04
(3209)
Timer 1 Sequence
Selection
Sets the drive response when sequence timer 1 is active.
0 : Digital Out Only
1 : Run
2 : Run - PID Disable
0
(0 - 2)
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...