10.6 MEMOBUS/Modbus Communications
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
757
Register No.
(Hex.)
Description
002C
Drive Status 2
bit 0
During Run
1: During Run
bit 1
During zero speed
1: During zero speed
bit 2
Speed agreement
1: During agreement
bit 3
User-defined speed agreement
1: During agreement
bit 4
Frequency Detection 1
1: Output frequency ≤ L4-01
bit 5
Frequency Detection 2
1: Output frequency ≥ L4-01
bit 6
Drive ready
1: Run ready
bit 7
During low voltage detection
1: During detection
bit 8
During baseblock
1: Drive output during baseblock
bit 9
Frequency reference mode
1: No communication option, 0: Communication option
bit A
Run command mode
1: No communication option, 0: Communication option
bit B
During overtorque/undertorque 1, 2 detection
bit C
Frequency reference loss
1: Loss
bit D
Executing Auto-Restart
1: Restart Enabled
bit E
Faults
1: Fault generated
bit F
MEMOBUS/Modbus communications timeout
1: At Timeout
Includes CE Go To Frequency alarm
002D
Drive Output Terminal Status
bit 0
Drive MFDO (terminal M1-M2)
1: ON, 0: OFF
bit 1
Drive MFDO (terminal M3-M4)
1: ON, 0: OFF
bit 2
Drive MFDO (terminal M5-M6)
1: ON, 0: OFF
bit 3 - 6
Reserved
bit 7
Drive Fault relay output (terminal MA/MB-MC)
1: ON, 0: OFF
bit 8 - F
Reserved
002E - 0030
Reserved
0031
U1-07 [DC Bus Voltage] (unit: 1 V)
0032
U1-09 [Torque Reference] (unit: 1%)
0033
Reserved
0034
Product code 1 [ASCII], product type (HV600 Bypass = 0G)
0035
Product code 2 [ASCII], product type (HV600 Bypass = 6B)
0036 - 0037
Reserved
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...