5.10 o: Keypad-Related Settings
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
367
■
o4-01: Elapsed Operating Time Setting
No.
(Hex.)
Name
Description
Default
(Range)
o4-01
(050B)
Elapsed Operating Time
Setting
Sets the initial value of the cumulative drive operation time in 10-hour units.
0 h
(0 - 9999 h)
When you select
o4-01
on the keypad, it will show the current value of
U4-01
in units of 10 hours (h). When you
change the setting of
o4-01
through the monitor, the
U4-01
count starts again as specified by the setting of
o4-01
.
Note:
Set this parameter in 10-hour (h) units. When
o4-01 = 30
,
U4-01 [Cumulative Ope Time] = 300 h
.
■
o4-02: Elapsed Operating Time Selection
No.
(Hex.)
Name
Description
Default
(Range)
o4-02
(050C)
Elapsed Operating Time
Selection
Sets the condition that counts the cumulative operation time.
1
(0, 1)
0 : U4-01 Shows Total Power-up Time
Counts the time from when you energize drive to when you de-energize the drive.
1 : U4-01 Shows Total RUN Time
Counts the time that the drive outputs voltage.
■
o4-03: Fan Operation Time Setting
No.
(Hex.)
Name
Description
Default
(Range)
o4-03
(050E)
Fan Operation Time Setting
Sets the value from which to start the cumulative drive cooling fan operation time in 10-hour units.
0 h
(0 - 9999 h)
Use monitor
U4-03 [Cooling Fan Ope Time]
to view the total operation time of the cooling fan. When you replace a
cooling fan, set
o4-03 = 0
to reset
U4-03
. Select
o4-03
on the keypad to show the current value of
U4-03
in 10-hour
(h) units. If you use the monitor to change
o4-03
, the recount of
U4-03
starts with the
o4-03
setting.
Note:
The drive sets
o4-03
in 10-hour (h) units. When
o4-03 = 30
,
U4-03 [Cooling Fan Ope Time]
will show
“
300 h
”
.
■
o4-05: Capacitor Maintenance Setting
No.
(Hex.)
Name
Description
Default
(Range)
o4-05
(051D)
Capacitor Maintenance
Setting
Sets the
U4-05 [CapacitorMaintenance]
monitor value.
0%
(0 - 150%)
When you replace a drive, set
o4-05 = 0
to reset
U4-05
. When the
o4-05
setting changes, the count of
U4-05
starts
again as specified by the setting of
o4-05
. After you complete the configuration,
o4-05
automatically resets to
0
.
Note:
The maintenance period changes for different operating environments.
■
o4-07: Softcharge Relay Maintenance Set
No.
(Hex.)
Name
Description
Default
(Range)
o4-07
(0523)
Softcharge Relay
Maintenance Set
Sets the
U4-06 [PreChargeRelayMainte]
monitor value.
0%
(0 - 150%)
When you replace a drive, set
o4-07 = 0
to reset
U4-06
. When the
o4-07
setting changes, the count of
U4-06
starts
again as specified by the setting of
o4-07
. After you complete the configuration,
o4-07
automatically resets to
0
.
Note:
The maintenance period changes for different operating environments.
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...