YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
637
◆
L6: Torque Detection
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
L6-01
(04A1)
Torque Detection
Selection 1
Sets the speed range that detects overtorque and undertorque and the operation of drives
(operation status) after detection.
0 : Disabled
1 : oL @ Speed Agree - Alarm only
2 : oL @ RUN - Alarm only
3 : oL @ Speed Agree - Fault
4 : oL @ RUN - Fault
5 : UL @ Speed Agree - Alarm only
6 : UL @ RUN - Alarm only
7 : UL @ Speed Agree - Fault
8 : UL @ RUN - Fault
9 : UL6 @ Speed Agree - Alarm only
10 : UL6 @ RUN - Alarm only
11 : UL6 @ Speed Agree - Fault
12 : UL6 @ RUN - Fault
0
(0 - 12)
L6-02
(04A2)
Torque Detection Level 1
Sets the detection level for Overtorque/Undertorque Detection 1. In V/f control, drive rated
output current = 100% value. In vector control, motor rated torque = 100% value.
15%
(0 - 300%)
L6-03
(04A3)
Torque Detection Time 1
Sets the detection time for Overtorque/Undertorque Detection 1.
10.0 s
(0.0 - 10.0 s)
L6-04
(04A4)
Torque Detection
Selection 2
Sets the speed range that detects overtorque and undertorque and the operation of drives
(operation status) after detection.
0 : Disabled
1 : oL @ Speed Agree - Alarm only
2 : oL @ RUN - Alarm only
3 : oL @ Speed Agree - Fault
4 : oL @ RUN - Fault
5 : UL @ Speed Agree - Alarm only
6 : UL @ RUN - Alarm only
7 : UL @ Speed Agree - Fault
8 : UL @ RUN - Fault
0
(0 - 8)
L6-05
(04A5)
Torque Detection Level 2
Sets the detection level for Overtorque/Undertorque Detection 2. In V/f control, drive rated
output current = 100% value. In vector control, motor rated torque = 100% value.
150%
(0 - 300%)
L6-06
(04A6)
Torque Detection Time 2
Sets the detection time for Overtorque/Undertorque Detection 2.
0.1 s
(0.0 - 10.0 s)
L6-13
(062E)
Motor Underload Curve
Select
Sets the motor underload protection (
UL6 [Undertorque Detection 6]
) based on motor load
and sets the level of
L6-02 [Torque Detection Level 1]
to refer to Fbase or Fmax.
0 : Base Frequency Enable
1 : Max Frequency Enable
0
(0, 1)
L6-14
(062F)
Motor Underload Level
@ Min Freq
Sets the
UL6 [Undertorque Detection 6]
detection level at minimum frequency by
percentage of drive rated current.
15%
(0 - 300%)
◆
L8: Drive Protection
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
L8-02
(04AE)
Overheat Alarm Level
Sets the
oH
detection level temperature.
Determined by o2-04
(50 - 150 °C)
L8-03
(04AF)
Overheat Pre-Alarm
Selection
Sets drive operation if it detects an
oH
alarm.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Operate at Reduced Speed (L8-19)
4
(0 - 4)
L8-05
(04B1)
Input Phase Loss
Protection Sel
Sets the function to enable and disable input phase loss detection.
0 : Disable
1 : Enabled
1
(0, 1)
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...