682
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
No.
(Hex.)
Name
Description
MFAO Signal Level
U5-30
(3000)
Time Hr Min HHMM
Shows the current time (Hours and Minutes).
No signal output available
U5-31
(3001)
Date Year
Shows the current year.
No signal output available
U5-32
(3002)
Date Mo Day MMDD
Shows the current date (Month and Date).
No signal output available
U5-33
(3003)
Date Week
Shows the current date of the week.
bit 0 : Sunday
bit 1 : Monday
bit 2 : Tuesday
bit 3 : Wednesday
bit 4 : Thursday
bit 5 : Friday
bit 6 : Saturday
bit 7 : Not used (normal value of 0).
No signal output available
U5-79
(3B9A)
PID Feedback Backup
Shows the
PID Feedback Backup [H3-xx = 24]
signal that the drive uses when it loses the
PID
Feedback [H3-xx = B]
.
Unit: 0.01%
Note:
Display unit and scaling are dependent on System Units.
No signal output available
U5-81
(3B9C)
Diff Level Source
Shows the Differential Feedback signal from the terminal set for
H3-xx = 2D [Differential Level
Source]
.
Unit: 0.00%
Note:
Unit and display scaling are dependent on System Units.
No signal output available
U5-99
(1599)
Setpoint
Shows the PID setpoint command.
Unit: 0.01%
Note:
Parameters
b5-46 [PID Unit Display Selection]
,
b5-38 [PID User Unit Display Scaling]
, and
b5-
39 [PID User Unit Display Digits]
set the unit, range, and resolution.
10 V = Maximum frequency
(-10 V to +10 V)
◆
U6: Operation Status Monitors
No.
(Hex.)
Name
Description
MFAO Signal Level
U6-01
(0051)
Iq Secondary Current
Shows the value calculated for the motor secondary current (q-Axis) as a percentage of the motor
rated secondary current.
Unit: 0.1%
10 V: Motor secondary rated
current (0 V to +10 V)
U6-17
(07D1)
Expert
Energy Save Coeff
Shows the total time of direction of motor rotation detections for Speed Estimation Speed Searches.
This value adjusts
b3-26 [Direction Determination Level]
.
Note:
Upper limit is +32767 and lower limit is -32767.
No signal output available
U6-21
(07D5)
Offset Frequency
Shows the total value of
d7-01 to d7-03 [Offset Frequency 1 to 3]
selected with
Add Offset
Frequency 1 to 3 [H1-xx = 44 to 46]
.
Unit: 0.1%
10 V: Maximum Frequency
U6-31
(007B)
TorqueDetect Monitor
Monitors the torque reference or the output current after applying the filter.
Unit: 0.1%
10 V:100%
U6-36
(0720)
Expert
Comm Errors-Host
Shows the number of inter-CPU communication errors. When you de-energize the drive, this value
resets to 0.
No signal output available
U6-37
(0721)
Expert
Comm Errors-Sensor
Shows the number of inter-CPU communication errors. When you de-energize the drive, this value
resets to 0.
No signal output available
U6-80
(07B0)
Option IP Address 1
Shows the currently available local IP Address (1st octet).
No signal output available
U6-81
(07B1)
Option IP Address 2
Shows the currently available local IP Address (2nd octet).
No signal output available
U6-82
(07B2)
Option IP Address 3
Shows the currently available local IP Address (3rd octet).
No signal output available
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...