10.6 MEMOBUS/Modbus Communications
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
753
Register No.
(Hex.)
Description
3A95
Emergency Override PID Feedback
PID feedback used during Emergency Override operation when you set
S6-02 = 2 or 3 [System PID Mode or Independent PID Mode]
and bit 4 of MEMOBUS
register 3A93H.
When
S6-02 = 2
, these parameters set the unit of the input value:
•
b5-38 [PID User Unit Display Scaling]
•
b5-39 [PID User Unit Display Digits]
•
b5-46 [PID Unit Display Selection]
When
S6-02 = 3
, these parameters set the unit of the input value:
•
S6-03 [EMOVR Independent PID Scale]
•
S6-04 [EMOVR Independent PID Unit]
•
S6-05 [EMOVR Independent PID Unit Digit]
3A96
Emergency Override PID Setpoint
PID Setpoint used during Emergency Override operation when you set
S6-02 = 2 or 3
and bit 5 of MEMOBUS register 3A93H.
When
S6-02 = 2
, these parameters set the unit of the input value:
•
b5-38
•
b5-39
•
b5-46
When
S6-02 = 3
, these parameters set the unit of the input value:
•
S6-03
•
S6-04
•
S6-05
8400
Bypass Command Word
bit 0
Reserved
bit 1
Reserved
bit 2
Reserved
bit 3
Remote Xfer
bit 4
Emergency Override Bypass
bit 5
Emergency Override (FWD)
bit 6
Motor OR
bit 7
Motor AND
bit 8
Reserved
bit 9
Reserved
bit 10
Reserved
bit 11
Drive Sel - Z1-39
bit 12
Bypass Sel - Z1-39
bit 13
Fault reset
bit 14
EFB
bit 15
Emergency Override Drive (REV)
8402
Bypass MFDI command
Controls the bypass digital inputs when
Z3-12 = 1 [Network Digital Inputs = Enabled]
.
bit 0
Multi-Function Input DI-1 (TB2-1)
bit 1
Multi-Function Input DI-2 (TB2-2)
bit 2
Multi-Function Input DI-3 (TB2-3)
bit 3
Multi-Function Input DI-4 (TB2-4)
bit 4
Multi-Function Input DI-5 (TB2-5)
bit 5
Multi-Function Input DI-6 (TB2-6)
bit 6
Multi-Function Input DI-7 (TB2-7)
bit 7
Multi-Function Input DI-8 (TB2-8)
All other bits
Reserved
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...