6.11 Diagnosing and Resetting Faults
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
519
Note:
If the drive receives a Run command from a communication option or control circuit terminal, the drive will not reset the fault. Remove the
Run command then try to clear the fault. If you do a fault reset when the drive has a Run command, the keypad will show minor fault
CrST
[Remove RUN Command to Reset]
.