4.5 Automatic Parameter Settings Optimized for Specific Applications (Application Presets)
168
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
6.
Push
or
to select
A1-06
, then push
.
7.
Push
or
to change the value, then push
.
The parameter setting procedure is complete.
Note:
•
You cannot change the value set in
A1-06
. To select an application preset, first set
A1-03 = 2220
to initialize parameters and then make a
selection to
A1-06
. If initializing all parameters will cause a problem, it is not necessary to change settings.
•
When the drive changes to the
A1-06
setting, it will also reset the parameters automatically registered to
A2-17 to A2-32 [User Parameters
17 to 32]
when
A2-33 = 1 [User Parameter Auto Selection = Enabled: Auto Save Recent Parms]
.
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...