YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
679
No.
(Hex.)
Name
Description
MFAO Signal Level
U4-18
(07DA)
Reference Source
Shows the selected frequency reference source.
The keypad shows the frequency reference source as
“
XY-nn
”
as specified by these rules:
X: Frequency reference
•
1:
b1-01 [Frequency Reference Selection 1]
Y-nn: Frequency reference source
•
0-01: Keypad (
d1-01 [Reference 1]
)
•
1-00: Analog input (unassigned)
•
1-01: MFAI terminal A1
•
1-02: MFAI terminal A2
•
2-02 to 2-17: Multi-step speed reference (
d1-02 to d1-17 [Reference 2 to 8, Jog Reference]
)
•
3-01: Serial communications
•
4-01: Communication option card
•
7-01: Reserved
•
9-01: Up/Down command
•
B-00: Hand Reference 1 (Analog)
•
B-01: Hand Reference 1 (
S5-05 [HAND Frequency Reference]
)
No signal output available
U4-19
(07DB)
Modbus FreqRef (dec)
Shows the frequency reference sent to the drive from the MEMOBUS/Modbus communications as a
decimal.
Unit: 0.01%
10 V: Maximum frequency
(0 V to +10 V)
U4-20
(07DC)
Option Freq Ref (dec)
Shows the frequency reference sent to the drive from the communication option as a decimal.
10 V: Maximum frequency
(0 V to +10 V)
U4-21
(07DD)
Run Command Source
Shows the selected Run command source.
The keypad shows the Run command source as
“
XY-nn
”
as specified by these rules:
X: Run command
•
0: OFF
•
1: AUTO
•
2: HAND
•
3: JOG, Emergency Override
Y: Run command source
•
0: Keypad
•
1: Control circuit terminal
•
3: Serial communications
•
4: Communication option card
•
7: Reserved
nn: Run command limit status data
•
00: No limit status.
•
01: The Run command stayed ON when the drive stopped in Programming Mode.
•
03: The Run command is in standby after the drive was energized until the soft charge bypass
contactor turns ON.
Note:
The drive will detect
Uv1 [DC Bus Undervoltage]
or
Uv [Undervoltage]
if the soft charge
bypass contactor does not turn ON after 10 s.
•
04: Will not restart after run stop.
•
05: An MFDI terminal cased a Fast stop or you pushed
on the keypad to ramp the motor
to stop.
•
06:
b1-17 = 0 [Run Command at Power Up = Disregard Existing RUN Command]
.
•
07: During baseblock while coast to stop with timer.
•
08: Frequency reference is less than
E1-09 [Minimum Output Frequency]
during baseblock.
•
09: Waiting for the Enter command from PLC.
No signal output available
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...