10.6 MEMOBUS/Modbus Communications
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
743
■
Communications Data
Communications data is a series of data that uses the combination of the communications register number and the data
for these registers. The data length changes when the description of the command changes. For a loopback test, it
switches to test code.
The communications register for the drive has a 2-byte length. Data that is written to the register for the drive is
usually 2 bytes. Register data that is read from the drive is also 2 bytes.
■
Error Check
Error check uses the CRC-16 method to detect transmission errors. Use the procedure in this section to calculate
CRC-16.
Command Data
When the drive receives data, it will make sure that there are no errors in the data. The drive uses the procedure below
to calculate CRC-16, then the drive compares that data with the CRC-16 value in the message. If the CRC-16 values
do not agree, the drive will not execute a command message.
When you calculate CRC-16 in MEMOBUS/Modbus communications, make sure that you set the start value as FFFF
(Hex.). All 16 bits must be 1.
Use this procedure to calculate CRC-16:
1. Make sure that the start value is FFFF (Hex.).
2. Calculate the FFFF (Hex.) start value and the XOR of the slave address (exclusive OR).
3. Move the step 2 results one column to the right. Do this shift until the carry bit is 1.
4. When the carry bit is 1, calculate XOR via the result from the above step 3 and A001 (Hex.).
5. Do steps 3 and 4 until the 8th shift to the right.
6. Use the result of step 5 to calculate the XOR and the data of the following messages (function code, register
address, data). Do steps 3 to 5 until the last data, then calculate.
7. The result of the last right shift or the value of the last XOR calculation is the result for CRC-16.
lists examples of the CRC-16 calculation of slave address 02 (Hex.) and function code 03 (Hex.). The
calculated results of CRC-16 for this section is D140 (Hex.).
Note:
The calculation example only gives information about some error checks with CRC-16. The drive will do the same error checks for the next
data.
Table 10.22 CRC-16 Calculation Example
Description
Calculation
Overflow
Description
Calculation
Overflow
Initial value (FFFF (Hex.))
1111 1111 1111 1111
-
Function code 03 (Hex.)
0000 0011
-
Address 02 (Hex.)
0000 0010
-
XOR w result
1000 0001 0011 1101
-
XOR w initial value
1111 1111 1111 1101
Shift 1
0100 0000 1001 1110
1
Shift 1
0111 1111 1111 1110
1
XOR w A001 (Hex.)
1010 0000 0000 0001
-
XOR w A001 (Hex.)
1010 0000 0000 0001
-
XOR result
1110 0000 1001 1111
-
XOR result
1101 1111 1111 1111
-
Shift 2
0111 0000 0100 1111
1
Shift 2
0110 1111 1111 1111
1
XOR w A001 (Hex.)
1010 0000 0000 0001
-
XOR w A001 (Hex.)
1010 0000 0000 0001
-
XOR result
1101 0000 0100 1110
-
XOR result
1100 1111 1111 1110
-
Shift 3
0110 1000 0010 0111
0
Shift 3
0110 0111 1111 1111
0
Shift 4
0011 0100 0001 0011
1
Shift 4
0011 0011 1111 1111
1
XOR w A001 (Hex.)
1010 0000 0000 0001
-
XOR w A001 (Hex.)
1010 0000 0000 0001
-
XOR result
1001 0100 0001 0010
-
XOR result
1001 0011 1111 1110
-
Shift 5
0100 1010 0000 1001
0
Shift 5
0100 1001 1111 1111
0
Shift 6
0010 0101 0000 0100
1
Shift 6
0010 0100 1111 1111
1
XOR w A001 (Hex.)
1010 0000 0000 0001
-
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...