336
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
■
L5-53: Thermostat Fault Retry Selection
No.
(Hex.)
Name
Description
Default
(Range)
L5-53
(3251)
Thermostat Fault Retry
Selection
Sets the drive to try an Auto Restart if it detects a
VLTS [Thermostat Fault]
fault.
1
(0, 1)
Note:
•
To use this function, set
S5-01 ≠ 0 [HAND Frequency Reference Source ≠ HAND Analog Input]
•
The drive will only restart after the Thermostat digital input deactivates and the
L5-04 [Interval Method Restart Time]
timer is expired.
0 : No Retry
1 : Retry
shows the drive operation for
VLTS
when
L5-53 = 1
and
L5-01 [Number of Auto-Restart Attempts] > 0
times
. The drive will wait for the Thermostat digital input to deac the
L5-04
time before it will restart.
H1-xx = 188: !Thermostat Fault
H2-xx = 95: Thermostat Fault
L5-04: Interval Method Restart Time
VLTS Fault: Thermostat Fault
Figure 5.83 Thermostat Fault Behavior
◆
L6: Torque Detection
The overtorque/undertorque/underload detection function prevents damage to machinery and loads.
Overtorque is when there is too much load on the machine. If the motor current or output torque is at the overtorque
detection level for the overtorque detection time, the drive will output an alarm and turn off the output.
Undertorque and underload are when a load suddenly decreases. When the motor current or output torque is at the
undertorque/underload detection level for the undertorque detection time, the drive will output an alarm and turn off
the output.
You can use the undertorque/undeload detection function to detect these conditions, for example:
•
Machine belt breaks
•
Unusual operation of the electromagnetic contactor on the drive output side
•
Clogged output side air filters in fans and blowers
Note:
If there is
oC [Overcurrent]
or
oL1 [Motor Overload]
, the drive can stop during overtorque conditions. Use torque detection to identify
overload conditions before the drive detects
oC
or
oL1
and stops. Use this function to detect problems in the application.
■
Parameter Setting
You can individually set the two overtorque/undertorque detection functions with the drive. Use the information in
to set the parameters.
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...