F7-20
(03F8)
EtherNet/IP Power
Scaling Factor
Sets the scaling factor for the power monitor in the EtherNet/IP Class ID 2AH Object.
0
(-15 - +15)
F7-21
(03F9)
EtherNet/IP Voltage Scale
Factor
Sets the scaling factor for the voltage monitor in the EtherNet/IP Class ID 2AH Object.
0
(-15 - +15)
F7-22
(03FA)
EtherNet/IP Time Scaling Sets the scaling factor for the time monitor in the EtherNet/IP Class ID 2AH Object.
0
(-15 - +15)
F7-23
(03FB)
Dynamic Out Param 1 for
CommCard
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values
from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for
each parameter. The drive will not write the values from Output Assembly 116 to the
registers when the MEMOBUS/Modbus address is 0. When you use a ProfiNet option, set
this parameter to set to configurable output 1.
0
F7-24
(03FC)
Dynamic Out Param 2 for
CommCard
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values
from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for
each parameter. The drive will not write the values from Output Assembly 116 to the
registers when the MEMOBUS/Modbus address is 0. When you use a ProfiNet option, set
this parameter to set to configurable output 2.
0
F7-25
(03FD)
Dynamic Out Param 3 for
CommCard
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values
from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for
each parameter. The drive will not write the values from Output Assembly 116 to the
registers when the MEMOBUS/Modbus address is 0. When you use a ProfiNet option, set
this parameter to set to configurable output 3.
0
F7-26
(03FE)
Dynamic Out Param 4 for
CommCard
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values
from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for
each parameter. The drive will not write the values from Output Assembly 116 to the
registers when the MEMOBUS/Modbus address is 0. When you use a ProfiNet option, set
this parameter to set to configurable output 4.
0
F7-27
(03FF)
Dynamic Out Param 5 for
CommCard
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values
from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for
each parameter. The drive will not write the values from Output Assembly 116 to the
registers when the MEMOBUS/Modbus address is 0. When you use a ProfiNet option, set
this parameter to set to configurable output 5.
0
F7-28
(0370)
Dynamic Out Param 6 for
CommCard
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values
from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for
each parameter. The drive will not write the values from Output Assembly 116 to the
registers when the MEMOBUS/Modbus address is 0.
0
F7-29
(0371)
Dynamic Out Param 7 for
CommCard
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values
from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for
each parameter. The drive will not write the values from Output Assembly 116 to the
registers when the MEMOBUS/Modbus address is 0.
0
F7-30
(0372)
Dynamic Out Param 8 for
CommCard
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values
from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for
each parameter. The drive will not write the values from Output Assembly 116 to the
registers when the MEMOBUS/Modbus address is 0.
0
F7-31
(0373)
Dynamic Out Param 9 for
CommCard
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values
from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for
each parameter. The drive will not write the values from Output Assembly 116 to the
registers when the MEMOBUS/Modbus address is 0.
0
F7-32
(0374)
Dynamic Out Param 10
for CommCard
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values
from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for
each parameter. The drive will not write the values from Output Assembly 116 to the
registers when the MEMOBUS/Modbus address is 0.
0
F7-33
(0375)
Dynamic In Param 1 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
When you use a ProfiNet option, set this parameter to set to configurable input 1.
0
F7-34
(0376)
Dynamic In Param 2 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
When you use a ProfiNet option, set this parameter to set to configurable input 2.
0
F7-35
(0377)
Dynamic In Param 3 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
When you use a ProfiNet option, set this parameter to set to configurable input 3.
0
F7-36
(0378)
Dynamic In Param 4 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
When you use a ProfiNet option, set this parameter to set to configurable input 4.
0
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...