YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
611
9.9
F: Options
◆
F6: Communication Options
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
F6-01
(03A2)
Communication Error
Selection
Sets the method to stop the motor or let the motor continue operating when the drive
detects
bUS [Option Communication Error]
.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Alarm (Run at d1-04)
5 : Alarm - Ramp Stop
1
(0 - 5)
F6-02
(03A3)
Comm External Fault
(EF0) Detect
Sets the conditions at which
EF0 [Option Card External Fault]
is detected.
0 : Always Detected
1 : Detected during RUN Only
0
(0, 1)
F6-04
(03A5)
bUS Error Detection
Time
Sets the delay time for the drive to detect
bUS [Option Communication Error]
.
Note:
When you install an option card in the drive, the parameter value changes to 0.0 s.
2.0 s
(0.0 - 5.0 s)
F6-08
(036A)
Comm Parameter Reset
@Initialize
Sets the function to initialize
F6-xx and F7-xx parameters
when the drive is initialized
with
A1-03 [Initialize Parameters]
.
0 : No Reset - Parameters Retained
1 : Reset Back to Factory Default
0
(0, 1)
F6-14
(03BB)
BUS Error Auto Reset
Sets the automatic reset function for
bUS [Option Communication Errors]
.
0 : Disabled
1 : Enabled
0
(0, 1)
F6-15
(0B5B)
Comm. Option
Parameters Reload
Sets the update method when you change
F6-xx, F7-xx [Communication Options]
.
0 : Reload at Next Power Cycle
1 : Reload Now
2 : Cancel Reload Request
0
(0 - 2)
◆
F7: Ethernet Options
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
F7-01
(03E5)
IP Address 1
Sets the first octet of the IP Address for the device that is connecting to the network.
Restart the drive after you change this parameter.
Note:
When
F7-13 = 0 [Address Mode at Startup = Static]
:
•
Use parameters
F7-01 to F7-04 [IP Address 4]
to set the IP Address. Be sure to set a
different IP address for each drive on the network.
•
Also set parameters
F7-01 to F7-12
.
192
(0 - 255)
F7-02
(03E6)
IP Address 2
Sets the second octet of the IP Address for the device that is connecting to the network.
Restart the drive after you change this parameter.
Note:
When
F7-13 = 0 [Address Mode at Startup = Static]
:
•
Use parameters
F7-01 to F7-04 [IP Address 4]
to set the IP Address. Be sure to set a
different IP address for each drive on the network.
•
Also set parameters
F7-01 to F7-12
.
168
(0 - 255)
F7-03
(03E7)
IP Address 3
Sets the third octet of the IP Address for the device that is connecting to the network.
Restart the drive after you change this parameter.
Note:
When
F7-13 = 0 [Address Mode at Startup = Static]
:
•
Use parameters
F7-01 to F7-04 [IP Address 4]
to set the IP Address. Be sure to set a
different IP address for each drive on the network.
•
Also set parameters
F7-01 to F7-12
.
1
(0 - 255)
F7-04
(03E8)
IP Address 4
Sets the fourth octet of the IP Address for the device that is connecting to the network.
Restart the drive after you change this parameter.
Note:
When
F7-13 = 0 [Address Mode at Startup = Static]
:
•
Use parameters
F7-01 to F7-04 [IP Address 4]
to set the IP Address. Be sure to set a
different IP address for each drive on the network.
•
Also set parameters
F7-01 to F7-12
.
20
(0 - 255)
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...