432
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Figure 5.100 Run Delay with Preset Speed Example: BAS Interlock Wait Time Fault
Figure 5.101 Run Delay with Preset Speed Example: Preset Speed
VFD RUN COMMAND
VFD OUTPUT FREQUENCY
DAMPER ACTUATOR OUTPUT
BAS INTERLOCK INPUT
2
t
1
t
VFD FREQUENCY REFERENCE
Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Interlock Run Select = 0 (Disabled)
Z1-14 Run Delay Frequency Reference = 60.0 Hz
Z1-15 Interlck Wait Time = 10.0 sec
Z1-15 Interlock Wait Time
t3
FAULT: FB02 BAS Ilock Open
VFD RUN COMMAND
VFD OUTPUT FREQUENCY
DAMPER ACTUATOR OUTPUT
BAS INTERLOCK INPUT
t1
t2
t3
VFD FREQUENCY REFERENCE
Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Interlock Run Select = 1 (Enable)
Z1-14 Run Delay Frequency Reference = 30.0 Hz
Z1-15 Interlck Wait Time = 0.0 sec (Never Time Out)
Z1-14 Run Delay Frequency Reference
t4
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...