YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
625
Setting Value
Function
Description
Ref.
117
!Torque Detection 1 (N.
C.)
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque >
L6-02 [Torque Detection Level 1]
, or the output current/torque <
L6-02
for longer
than the time set in
L6-03 [Torque Detection Time 1]
.
118
!Torque Detection 2 (N.
O.)
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque >
L6-05 [Torque Detection Level 2]
, or the output current/torque <
L6-05
for longer
than the time set in
L6-06 [Torque Detection Time 2]
.
119
!Torque Detection 2 (N.
C.)
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque >
L6-05 [Torque Detection Level 2]
, or the output current/torque <
L6-05
for longer
than the time set in
L6-06 [Torque Detection Time 2]
.
11A
!During Reverse
The terminal deactivates when the motor operates in the reverse direction.
ON : The motor is operating in the forward direction or the motor stopped.
OFF : The motor is operating in the reverse direction.
11B
!During Baseblock (N.C.) The terminal activates during baseblock. When the drive is in baseblock, the drive output transistor stops switching
and does not make DC bus voltage.
ON : During baseblock.
OFF : The drive is not in baseblock.
11E
!Executing Auto-Restart
The terminal deactivates when the Auto Restart function is trying to restart after a fault.
11F
!Motor Overload Alarm
(oL1)
The terminal deactivates when the electronic thermal protection value of the motor overload protective function is a
minimum of 90% of the detection level.
120
!Drive Overheat Pre-
Alarm (oH)
The terminal deactivates when the drive heatsink temperature is at the level set with
L8-02 [Overheat Alarm Level]
.
121
!Safe Torque OFF
The terminal deactivates (safety stop state) when the safety circuit and safety diagnosis circuit are operating correctly
and when terminals H1-HC and H2-HC are OFF (Open).
ON : Safety circuit fault or RUN/READY
OFF : Safety stop state
12F
!Maintenance
Notification
The terminal deactivates when drive components are at their estimated maintenance period.
Tells the user about the maintenance period for these items:
•
IGBT
•
Cooling fan
•
Capacitor
•
Soft charge bypass relay
137
!During Frequency
Output
The terminal deactivates when the drive outputs frequency.
ON : The drive does not output frequency.
OFF : The drive outputs frequency.
138
!Drive Enabled
This terminal deactivates when the
H1-xx = 6A [Drive Enable]
terminal deactivates.
139
!Watt Hour Pulse Output
Outputs the pulse that shows the watt hours.
13A
!Drive Overheat Alarm
The terminal deactivates when the drive heatsink temperature is at the
L8-02 [Overheat Alarm Level]
setting while
L8-
03 = 4 [Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)]
and the drive is running.
13D
!During Speed Search
The terminal deactivates when the drive is doing speed search.
142
!Pressure Reached
The terminal deactivates when the drive is at the Pressure Setpoint.
14C
!During Fast Stop
The terminal deactivates when the fast stop is in operation.
14D
!oH Pre-Alarm Reduction
Limit
The terminal deactivates when
L8-03 = 4 [Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)]
and
oH [Heatsink Overheat]
does not clear after the drive decreases the frequency for 10 cycles.
151
!Sequence Timer 1
The terminal deactivates when Sequence Timer 1 is active.
152
!Sequence Timer 2
The terminal deactivates when Sequence Timer 2 is active.
153
!Sequence Timer 3
The terminal deactivates when Sequence Timer 3 is active.
154
!Sequence Timer 4
The terminal deactivates when Sequence Timer 4 is active.
158
!UL6 Underload Detected The terminal deactivates when the drive detected
UL6 [Underload or Belt Break Detected]
.
160
!Internal Cooling Fan
Failure
The terminal deactivates when the drive detects a cooling fan failure in the drive.
162
!Modbus Reg 1 Status
Satisfied
The terminal deactivates when the bit specified by
H2-08 [Modbus Register 1 Bit Select]
for the MEMOBUS register
address set with
H2-07 [Modbus Register 1 Address Select]
activates.
163
!Modbus Reg 2 Status
Satisfied
The terminal deactivates when the bit specified by
H2-10 [Modbus Register 2 Bit Select]
for the MEMOBUS register
address set with
H2-09 [Modbus Register 2 Address Select]
activates.
169
!External Power 24V
Supply
The terminal deactivates when there is an external 24V power supply between terminals PS-AC.
ON : An external 24V power supply does not supply power.
OFF : An external 24V power supply supplies power.
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...