6.3 Faults, Minor Faults, Alarms, and Error Codes Listed Alphabetically
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
459
6.3
Faults, Minor Faults, Alarms, and Error Codes Listed
Alphabetically
shows the possible fault, minor fault, alarm, and error codes.
The display codes are in alphabetical order. Search the table for the code shown on the keypad, and identify its causes
and possible solutions.
Drive Faults thrown by the HV600 drive will stop the bypass from running the drive but will not stop it from running
in Bypass Mode.
System Faults will stop the drive and also keep it from running in Bypass Mode.
Note:
The number in parentheses adjacent to the code in the table identifies the fault code or minor fault code (hex. number) that was read during
MEMOBUS/Modbus communications.
Example: AFBL (00A2)
Table 6.2 List of Fault, Minor Fault, Alarm, and Error Codes
Display (Hex.)
Name
ALM LED
Type
Ref.
AFBL (00A2)
Analog Fbk Lost, Switched to Net
Flashing
Alarm
AL02 (00B2)
Interlock Open
Flashing
Alarm
AL03 (00B3)
Emergency Override Bypass
Flashing
Alarm
AL09 (00B9)
Restart Delay Active
Flashing
Alarm
AL13 (00BD)
Loss of Load Detected
Flashing
Alarm
AL16 (00C0)
Input Phase Rotation
Flashing
Alarm
AL17 (00C1)
Remote Xfer disabled in Reverse
Flashing
Alarm
AL18 (00C2)
Auto Xfer disabled in Reverse
Flashing
Alarm
AuDis (00A3)
Low PI Aux Fdbk Drive Disabled
Flashing
Alarm
AuFbl (00A5)
PI Aux Fdbk Lost Switched to Net
Flashing
Alarm
AUXFB (00A4)
PI Aux Feedback Level Loss
Flashing
Alarm
AUXFB (0420)
PI Aux Feedback Level Loss
Illuminated
Drive Fault
bAT (0085)
Keypad Battery Low Voltage
Flashing
Alarm
bAT (0402)
Keypad Battery Low Voltage
Illuminated
Drive Fault
bb (0008)
Baseblock
Flashing
Alarm
bCE (0416)
Bluetooth Communication Fault
Illuminated
Drive Fault
bCE (008A)
Bluetooth Communication Error
Flashing
Alarm
BuDif (00A6)
Main Fdbk Lost, Using Diff Fdbk
Flashing
Alarm
Bu-Fb (0090)
Main Fdbk Lost Using Backup Fdbk
Flashing
Alarm
BuFbl (0091)
Backup Fdbk Lost Chk/Repl Xducer
Flashing
Alarm
bUS (0015)
Option Communication Error
Flashing
Alarm
bUS (0022)
Option Communication Error
Illuminated
Drive Fault
bUSy
Busy
-
Not an alarm.
CALL (001D)
Serial Comm Transmission Error
Flashing
Alarm
CE (0092)
Run at H5-34 (CE Go-To-Freq)
Flashing
Alarm
CE (0014)
Modbus Communication Error
Flashing
Alarm
CE (0021)
Modbus Communication Error
Illuminated
Drive Fault
CoF (0046)
Current Offset Fault
Illuminated
Drive Fault
CPF00 (0081)
Control Circuit Error
Illuminated
Drive Fault
CPF01 (0082)
Control Circuit Error
Illuminated
Drive Fault
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...