Remove the Saved Frequency Reference Value
The procedure to remove the saved frequency reference value is different for different functions. Use these methods
to remove the value:
•
Release the input programmed for
Accel/Decel Ramp Hold [H1-xx = A]
.
•
Set an Up or Down command while no Run command is active.
■
d4-10: Up/Down Freq Lower Limit Select
No.
(Hex.)
Name
Description
Default
(Range)
d4-10
(02B6)
Up/Down Freq Lower Limit
Select
Sets the lower frequency limit for the Up/Down function.
0
(0, 1)
0 : Greater of d2-02 or Analog
The higher value between
d2-02 [Frequency Reference Lower Limit]
and an analog input programmed for
Frequency
Reference [H3-02, H3-10 = 0]
sets the lower frequency reference limit.
Note:
When you use
External Reference 1/2 Selection [H1-xx = 2]
to switch between the Up/Down function and an analog input as the reference
source, the analog value becomes the lower reference limit when the Up/Down command is active. Set
d4-10 = 1
to isolate the Up/Down
function and the analog input value.
1 : d2-02
You can only use
d2-02
to set the lower limit of the frequency reference.
◆
d6: Field Weakening
d6 parameters
set the field weakening function.
The field weakening function decreases the energy consumption of the motor. It decreases the output voltage of the
drive to a set level. The function decreases the motor excitation current inversely proportional to speed in a constant
output range, and does not let the induced voltage of the motor become more than the power supply voltage. To
enable this function, set
Field Weakening [H1-xx = 63]
ON.
Note:
Use the Field Weakening function in constant light-load applications. To control the energy consumption of the motor for other load
conditions, use the
b8 parameters [Energy Saving]
.
■
d6-01: Field Weakening Level
No.
(Hex.)
Name
Description
Default
(Range)
d6-01
(02A0)
Field Weakening Level
Sets the drive output voltage as a percentage of
E1-05 [Maximum Output Voltage]
when
H1-xx = 63
[Field Weakening]
is activated.
80%
(0 - 100%)
■
d6-02: Field Weakening Frequency Limit
No.
(Hex.)
Name
Description
Default
(Range)
d6-02
(02A1)
Field Weakening Frequency
Limit
Sets the minimum output frequency to start field weakening.
0.0 Hz
(0.0 - 400.0 Hz)
To enable the Field Weakening command, make sure that these two conditions are true:
•
The output frequency ≥
d6-02
.
•
There is a speed agreement status.
◆
d7: Offset Frequency
The drive will use 3 digital signal inputs, to add or subtract the set frequency (Offset frequency) to/from the frequency
reference and correct the speed. The drive uses the terminal set in
H1-xx = 44 to 46 [MFDI Function Select = Add
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...