5.1 A: Initialization Parameters
176
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
3. Set
A1-03 = 1110
to reset to the saved parameter settings.
When you initialize the drive, the drive sets the parameter values to the User Parameter setting values.
2220 : 2-Wire Initialization
Resets all parameters to default settings.
The drive will not initialize the parameters in
when
A1-03 = 2220
.
Table 5.2 Parameters that are not Initialized Using a 2-Wire Sequence (2220)
No.
Name
A1-00
Language Selection
E1-03
V/f Pattern Selection
F6-08
Comm Parameter Reset @Initialize
F6-xx/F7-xx
Communication Option Parameters
Set
F6-08 = 1 [Comm Parameter Reset @Initialize = Reset Back to Factory Default]
to initialize communication option
card parameters.
L8-35
Installation Method Selection
o2-04
Drive Model (KVA) Selection
o2-24
LED Light Function Selection
Note:
•
Set
A1-06 [Application Preset]
to let the drive automatically set the best parameter settings for the selected application.
•
When
A1-03 = 2220
, the drive automatically sets
A1-05 [Password Setting] = 0000
. Make sure that you set the password again for
applications where a password is necessary.
■
A1-04: Password
No.
(Hex.)
Name
Description
Default
(Range)
A1-04
(0104)
Password
Entry point for the password set in
A1-05 [Password Setting]
. The user can view the settings of
parameters that are locked without entering the password. Enter the correct password in this
parameter to change parameter settings.
0000
(0000 - 9999)
If the password entered in
A1-04
does not agree with the password setting in
A1-05
, you cannot change these
parameters:
•
A1-01 [Access Level Selection]
•
A1-03 [Initialize Parameters]
•
A1-06 [Application Preset]
•
A2-01 to A2-32 [User Parameter 1 to 32]
To lock parameter settings after making changes without changing the password, enter the incorrect password in
A1-
04
and push
.
Enter the Password to Unlock Parameters
Use this procedure to unlock parameter settings.
Set the password in
A1-05 [Password Setting]
, and show the Parameter Setting Mode screen on the keypad.
This procedure verifies the password, and makes sure that the parameter settings are unlocked.
1.
Push
or
to select “A: Initialization Parameters”, then push
.
2.
Push
or
to select
[A1-04]
, then push
.
You can now change parameter settings.
3.
Push
or
to move the digit and enter the password.
4.
Push
to confirm the password.
The drive unlocks the parameters and automatically shows the Parameters Screen.
5.
Push
or
to show
[A1-06]
, then push
.
The keypad shows the setting value for
[A1-06]
.
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...