608
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
◆
d4: Frequency Ref Up/Down & Hold
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
d4-01
(0298)
Freq Reference Hold
Selection
Sets the function that saves the frequency reference after a Stop command or when de-
energizing the drive.
Set
H1-xx [MFDI Function Selection]
to one of these values to enable this parameter:
•
A [Accel/Decel Ramp Hold]
•
10/11 [Up/Down Command]
0 : Disabled
1 : Enabled
0
(0, 1)
d4-10
(02B6)
Up/Down Freq Lower
Limit Select
Sets the lower frequency limit for the Up/Down function.
0 : Greater of d2-02 or Analog
1 : d2-02
0
(0, 1)
◆
d6: Field Weakening
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
d6-01
(02A0)
Field Weakening Level
Sets the drive output voltage as a percentage of
E1-05 [Maximum Output Voltage]
when
H1-xx = 63 [Field Weakening]
is activated.
80%
(0 - 100%)
d6-02
(02A1)
Field Weakening
Frequency Limit
Sets the minimum output frequency to start field weakening.
0.0 Hz
(0.0 - 400.0 Hz)
◆
d7: Offset Frequency
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
d7-01
(02B2)
RUN
Offset Frequency 1
Uses
H1-xx = 44 [MFDI Function Select = Add Offset Frequency 1 (d7-01)]
as a
percentage of the Maximum Output Frequency to add or subtract the set frequency to/from
the frequency reference.
0.0%
(-100.0 - +100.0%)
d7-02
(02B3)
RUN
Offset Frequency 2
Uses
H1-xx = 45 [MFDI Function Select = Add Offset Frequency 2 (d7-02)]
as a
percentage of the Maximum Output Frequency to add or subtract the set frequency to/from
the frequency reference.
0.0%
(-100.0 - +100.0%)
d7-03
(02B4)
RUN
Offset Frequency 3
Uses
H1-xx = 46 [MFDI Function Select = Add Offset Frequency 3 (d7-03)]
as a
percentage of the Maximum Output Frequency to add or subtract the set frequency to/from
the frequency reference.
0.0%
(-100.0 - +100.0%)
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...