Figure 5.56 Reverse Operation Output Time Chart
■
1B: During Baseblock (N.C.)
Setting Value
Function
Description
1B
During Baseblock (N.C.)
The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops switching and does not
make DC bus voltage.
ON : The drive is not in baseblock.
OFF : During baseblock
■
1E: Executing Auto-Restart
Setting Value
Function
Description
1E
Executing Auto-Restart
The terminal activates when the Auto Restart function is trying to restart after a fault.
The terminal deactivates when the Auto Restart function automatically resets a fault. The terminal deactivates when
the Auto Restart function detects the fault again because there were too many restart attempts as specified by
L5-01
[Number of Auto Restart Attempts]
.
Note:
Refer to
for more information.
■
1F: Motor Overload Alarm (oL1)
Setting Value
Function
Description
1F
Motor Overload Alarm
(oL1)
The terminal activates when the electronic thermal protection value of the motor overload protective function is a minimum of 90%
of the detection level.
Note:
Refer to
“
L1-01: Motor Overload (oL1) Protection
”
for more information.
■
20: Drive Overheat Pre-Alarm (oH)
Setting Value
Function
Description
20
Drive Overheat Pre-Alarm
(oH)
The terminal activates when the drive heatsink temperature is at the level set with
L8-02 [Overheat Alarm Level]
.
Note:
Refer to
“
L8-02: Overheat Alarm Level
”
for more information.
■
21: Safe Torque OFF
Setting Value
Function
Description
21
Safe Torque OFF
The terminal activates (safety stop state) when the safety circuit and safety diagnosis circuit are operating correctly and when
terminals H1-HC and H2-HC are OFF (Open).
Note:
EDM = External Device Monitor
ON : Safety stop state
Terminals H1-HC and H2-HC are OFF (Open) (safety stop state).
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...