YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
425
Note:
•
Set
YF-01 = 1 [PI Aux Control Selection = Enabled]
and
YF-09 [PI Aux Control Low Level Detect]
> 0 to enable PI Aux Low Level
Detection.
•
Parameter
YF-10
only applies when
YF-11 = 2 or 3
.
0 : No Display
When the PI Aux Feedback decreases to less than the
YF-09 [PI Aux Control Low Level Detect]
level, the digital
output set for
H2-xx = 9E [MFDO Function Selection = Low PI Auxiliary Control Level
will activate. When the level
increases to more than the
YF-09
level, the digital output will immediately deactivate.
1 : Alarm Only
When the PI Aux Feedback decreases to less than
YF-09
level, the keypad will show an
LOAUX [Low PI Aux
Feedback Level]
alarm and the digital output set for
H2-xx = 9E
will activate. When the feedback increases to more
than
YF-09
level, the drive will clear the alarm and the digital output will deactivate.
2 : Fault
When the output frequency is more than zero, and the PI Aux Feedback decreases to less than the
YF-09
level, the
digital output set for
H2-xx = 9E
and an
LOAUX
alarm will immediately activate. If the feedback stays less than the
YF-09
level for the time set in
YF-10 [PI Aux Low Level Detection Time]
, the drive will detect an
LOAUX [Low PI
Aux Feedback Level]
fault.
3 : Auto-Restart (time set by YF-15)
When the output frequency is more than zero, and the PI Aux Feedback decreases to less than the
YF-09
level, the
digital output set for
H2-xx = 9E
and an
LOAUX
alarm will immediately activate. If the feedback stays less than the
YF-09
level for the time set in
YF-10 [PI Aux Low Level Detection Time]
, the drive will detect an
LOAUX
fault.
When
L5-01 [Number of Auto-Restart Attempts]
> 0 and if the drive detects an
LOAUX
fault, the drive will
automatically try an Auto-Restart after
YF-15 [PI Aux Level Detect Restart Time]
is expired. If the feedback is not
more than the
YF-09
level, the Auto-Restart counter will increment and the drive will stay faulted.
■
YF-12: PI Aux Control High Level Detect
No.
(Hex.)
Name
Description
Default
(Range)
YF-12
(3F5B)
RUN
PI Aux Control High Level
Detect
Sets the value above which the level must be for longer than
YF-13 [PI Aux High Level Detection
Time]
to respond as specified by
YF-14 [PI Aux Hi Level Detection Select]
.
0.0 PSI
(-999.9 - +999.9 PSI)
Note:
•
Set this parameter to 0.0 to disable the function.
•
Parameter
YF-13
only applies to when
YF-14 = 2 and 3 [Fault and Auto-Restart (time set by YF-15)]
.
•
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level Decimal Place Pos]
set the unit and resolution.
■
YF-13: PI Aux High Level Detection Time
No.
(Hex.)
Name
Description
Default
(Range)
YF-13
(3F5C)
RUN
PI Aux High Level
Detection Time
Sets the length of time that the level must be more than
YF-12 [PI Aux Control High Level Detect]
before the drive will respond when
YF-14 = 2, 3 [PI Aux Hi Level Detection Select]
.
0.1 s
(0.0 - 300.0 s)
■
YF-14: PI Aux Control Hi Level Det Sel
No.
(Hex.)
Name
Description
Default
(Range)
YF-14
(3F5D)
PI Aux Control Hi Level Det
Sel
Sets the drive response when the PI Aux Feedback increases to more than the
YF-12 [PI Aux Control
High Level Detect]
level for longer than the time set in
YF-13 [PI Aux High Level Detection Time]
.
1
(0 - 3)
Note:
•
Set
YF-01 = 1 [PI Aux Control Selection = Enabled]
and
YF-12 [PI Aux Control High Level Detect]
> 0 to enable PI Aux High Level
Detection.
•
Parameter
YF-13
only applies when
YF-14 = 2 or 3
0 : NoDisplay (Digital Output Only)
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...