YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
251
Doing Auto-Tuning automatically sets the
E2 parameters
to the optimal values. If you cannot do Auto-Tuning, set the
E2 parameters
manually.
■
E2-01: Motor Rated Current (FLA)
No.
(Hex.)
Name
Description
Default
(Range)
E2-01
(030E)
Motor Rated Current (FLA)
Sets the motor rated current in amps.
Determined by o2-04
(10% to 200% of the drive
rated current)
Note:
•
If
E2-01 < E2-03 [Motor No-Load Current]
the drive will detect
oPE02 [Parameter Range Setting Error]
.
•
The default settings and setting ranges are in these units:
–
0.01 A: D002 to D046, A002 to A042, B001 to B014
–
0.1 A: D059 to D273, A054 to A248, B021 to B302
The value set for
E2-01
becomes the reference value for motor protection and the torque limit. Enter the motor rated
current as written on the motor nameplate. The value of
E2-01
is automatically set to the value input for
“
Motor Rated
Current
”
by the Auto-Tuning process.
■
E2-02: Motor Rated Slip
No.
(Hex.)
Name
Description
Default
(Range)
E2-02
(030F)
Motor Rated Slip
Sets motor rated slip.
Determined by o2-04
(0.000 - 20.000 Hz)
This parameter value becomes the base slip compensation value. The drive automatically sets this parameter during
Auto-Tuning. When you cannot do Auto-Tuning, calculate the motor rated slip with the information on the motor
nameplate and this formula:
E2-02
= f - (n × p) / 120
•
f: Motor rated frequency (Hz)
•
n: Rated motor speed (min
-1
(r/min))
•
p: Number of motor poles
■
E2-03: Motor No-Load Current
No.
(Hex.)
Name
Description
Default
(Range)
E2-03
(0310)
Motor No-Load Current
Sets the no-load current for the motor in amps when operating at the rated frequency and the no-load
voltage.
Determined by o2-04
(0 to E2-01)
Note:
The default settings and setting ranges are in these units:
•
0.01 A: D002 to D046, A002 to A042, B001 to B014
•
0.1 A: D059 to D273, A054 to A248, B021 to B302
The drive automatically sets this parameter during Auto-Tuning. When you cannot do Auto-Tuning, you can also use
the motor no-load current on the motor test report to enter this value manually. Contact the motor manufacturer to
receive a copy of the motor test report.
Note:
The default setting of the no-load current is for operation with a 4-pole motor recommended by Yaskawa.
■
E2-04: Motor Pole Count
No.
(Hex.)
Name
Description
Default
(Range)
E2-04
(0311)
Motor Pole Count
Sets the number of motor poles.
4
(2 - 120)
Auto-Tuning automatically sets this parameter to the value of [Number of Motor Poles].
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...