668
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
Z2-08
(856A)
Digital Input 8 Function
(TB2-8)
Sets the function for bypass digital input 8.
0
(0 - 47)
Z2-09
(856B)
Digital Input 1 Invert
Select
Inverts the output of the function selected in Digital Input 1.
0 : Normal (Non-inverted)
1 : Inverted
0
(0, 1)
Z2-10
(856C)
Digital Input 2 Invert
Select
Inverts the output of the function selected in Digital Input 2.
0 : Normal (Non-inverted)
1 : Inverted
0
(0, 1)
Z2-11
(856D)
Digital Input 3 Invert
Select
Inverts the output of the function selected in Digital Input 3.
0 : Normal (Non-inverted)
1 : Inverted
0
(0, 1)
Z2-12
(856E)
Digital Input 4 Invert
Select
Inverts the output of the function selected in Digital Input 4.
0 : Normal (Non-inverted)
1 : Inverted
0
(0, 1)
Z2-13
(856F)
Digital Input 5 Invert
Select
Inverts the output of the function selected in Digital Input 5.
0 : Normal (Non-inverted)
1 : Inverted
0
(0, 1)
Z2-14
(8570)
Digital Input 6 Invert
Select
Inverts the output of the function selected in Digital Input 6.
0 : Normal (Non-inverted)
1 : Inverted
0
(0, 1)
Z2-15
(8571)
Digital Input 7 Invert
Select
Inverts the output of the function selected in Digital Input 7.
0 : Normal (Non-inverted)
1 : Inverted
0
(0, 1)
Z2-16
(8572)
Digital Input 8 Invert
Select
Inverts the output of the function selected in Digital Input 8.
0 : Normal (Non-inverted)
1 : Inverted
0
(0, 1)
Z2-23
(8579)
Digital Output 7 (TB1
1~3)
Sets the function for bypass digital output 7.
7
(0 - 99)
Z2-24
(857A)
Digital Output 8 (TB1
4~6)
Sets the function for bypass digital output 8.
10
(0 - 99)
Z2-25
(857B)
Digital Output 9 (TB1
7~9)
Sets the function for bypass digital output 9.
12
(0 - 99)
Z2-26
(857C)
Digital Output 10 (TB1
10~12)
Sets the function for bypass digital output 10.
15
(0 - 99)
Z2-30
(8580)
Analog Input Signal
Level Select
Sets the input signal level for MFAI terminal A1.
0 : 0 to 10V (Lower Limit at 0)
2 : 4 to 20 mA
3 : 0 to 20 mA
0
(0 - 3)
Z2-32
(8582)
Analog Input Gain
Setting
Sets the gain of the analog signal input to MFAI terminal A1.
100.0%
(-999.9 - +999.9%)
Z2-33
(8583)
Analog Input Bias Setting Sets the bias of the analog signal input to MFAI terminal A1.
0.0%
(-999.9 - +999.9%)
■
Z2-xx: Digital Input Setting Values
Setting Value
Function
Description
Ref.
0
Not Used
Use this setting for unused terminals or to use terminals in through mode.
1
Drive S1 Passthrough
Drive Multi-function input S1.
2
Drive S2 Passthrough
Drive Multi-function input S2.
3
Drive S3 Passthrough
Drive Multi-function input S3.
4
Drive S4 Passthrough
Drive Multi-function input S4.
5
Drive S5 Passthrough
Drive Multi-function input S5.
6
Drive S6 Passthrough
Drive Multi-function input S6.
7
Drive S7 Passthrough
Drive Multi-function input S7.
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...