YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
391
Table 5.59 Drive Operation in Normal Mode
b1-02 Settings
HOA Modes Transition
0 to 3
7 to 9
When you use the MFDIs set for
H1-xx = 6D and 6E [AUTO Command and HAND Command]
,
and
on
the HOA keypad do not function. When
S5-04 = 1
, use these MFDIs together.
Table 5.60 MFDI Settings and Drive Operation in Normal Mode
H1-xx = 6D
[AUTO Command]
H1-xx = 6E
[HAND Command]
Operation Mode
Frequency Reference Source
Run Command Source
OFF
OFF
OFF
Based on
b1-01
-
OFF
ON
HAND
Based on
S5-01
Keypad
ON
OFF
AUTO
Based on
b1-01
Based on
b1-02
ON
ON
OFF
Based on
b1-01
-
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...