YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
669
Setting Value
Function
Description
Ref.
21
Run (AUTO)
Starts and stops the bypass.
22
Run Enable - Safety (NC) Stops the bypass.
23
Run Interlock (BAS)
Stops the drive and triggers alarm
AL02
24
Remote Transfer to
Bypass
Stops the drive and turns on the bypass when a Run command is issued while in Drive Mode.
25
Emergency Override
Bypass
Stops the drive and turns on the bypass when a Run command is issued while in Drive Mode.
26
Emergency Override
Drive (FWD)
The bypass controller stays in this state even if the drive faults or is unavailable.
27
Motor OR Select
2-Motor OR function; 0/1 for Motor 1/2.
28
Motor AND Select
2-Motor AND function; 0/1 for 1/2 motor.
29
External Overload Motor
1 (NC)
When input is open, it will trigger an
oL
fault and open bypass (K3) contactors.
30
External Overload Motor
2 (NC)
When input is open, it will trigger an
oL
fault and open bypass (K3) contactors.
31
HAND Select
The HAND function command will come from a digital input and the unit ignores the HAND key on the HOA
operator.
32
AUTO Select
The AUTO function command will come from a digital input and the unit ignores the AUTO key on the HOA
operator.
33
Drive/Bypass Select
The DRIVE/BYPASS select function command will come from a digital input, and the unit ignores the DRV/BYP key
on the HOA operator.
ON : Bypass Mode is selected
OFF : Drive Mode is selected
34
Fault Reset
Resets any faults that are present.
35
External Fault (EF0)
Issues external fault
EF0
from the bypass to the drive.
36
External Fault (EFB)
Triggers external fault
EFB
on the bypass.
37
Run Reverse (AUTO)
Starts and stops the bypass in reverse.
38
Fire Stat Switch (NC)
Stops the drive from running and shows
“
Fire Stat
”
on the keypad.
39
Freeze Stat Switch (NC)
Stops the drive from running and shows
“
Freeze Stat
”
on the keypad.
40
Smoke Alarm (NC)
Stops the drive from running and shows
“
Smoke Alarm
”
on the keypad.
41
OverPressure Switch
(NC)
Stops the drive from running and shows
“
OverPressure
”
on the keypad.
42
Low Suction Switch (NC) Stops the drive from running and shows
“
Low Suction
”
on the keypad.
43
Vibration Switch (NC)
Stops the drive from running and shows
“
Vibration
”
on the keypad.
44
Emergency Override
Drive (REV)
The bypass controller stays in this state even if the drive faults or is unavailable.
45
Serial Hardware Test
(RS-485)
46
Low City Pressure
Indicates that sufficient or insufficient pressure is present on the inlet to the pump. Used mainly for pressure booster
situations.
47
Motor Preheat
Sets the command to apply the motor pre-heat current.
■
Z2-xx: Digital Output Setting Values
Setting Value
Function
Description
Ref.
0
Serial Communication
Control
Set when serial communications controls the bypass.
1
K1 Drive Input Contactor Set when the K1 contactor is closed.
2
K2 Drive Output
Contactor
Set when the K2 contactor is closed.
3
K3 Bypass Contactor
Set when the K3 contactor is closed.
4
K4 Motor 1 Contactor
Set when the K4 contactor is closed.
5
K5 Motor 2 Contactor
Set when the K5 contactor is closed.
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...