YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
269
Setting
Signal Input Method from
Peripheral Devices
External Fault Detection Method
Stopping Method
N.O.
N.C.
Always
Detected
Detected during
RUN Only
Ramp to Stop
(Fault)
Coast to Stop
(Fault)
Fast Stop
(Fault)
Continuous
Operation
(Alarm Only)
23
-
x
-
x
x
-
-
-
24
x
-
x
-
-
x
-
-
25
-
x
x
-
-
x
-
-
26
x
-
-
x
-
x
-
-
27
-
x
-
x
-
x
-
-
28
x
-
x
-
-
-
x
-
29
-
x
x
-
-
-
x
-
2A
x
-
-
x
-
-
x
-
2B
-
x
-
x
-
-
x
-
2C
x
-
x
-
-
-
-
x
2D
-
x
x
-
-
-
-
x
2E
x
-
-
x
-
-
-
x
2F
-
x
-
x
-
-
-
x
*1
Set the terminal to N.O. (detects external fault when switched ON) or N.C. (detects external fault when switched OFF).
*2
Set the drive to always detect each fault or to detect only during run.
■
30: PID Integrator Reset
Setting Value
Function
Description
30
PID Integrator Reset
Sets the command to reset and hold the PID control integral to 0 when the terminal is ON.
Note:
Refer to
“
PID control block diagram
”
for more information.
■
31: PID Integrator Hold
Setting Value
Function
Description
31
PID Integrator Hold
Sets the command to hold the integral value of the PID control while the terminal is activated.
When you turn off the input terminal, PID control restarts the integral.
Note:
Refer to
“
PID control block diagram
”
for more information.
■
34: PID Soft Starter Disable
Setting Value
Function
Description
34
PID Soft Starter Disable
Sets the PID soft starter function.
ON : Disabled
Disables
b5-17 [PID Accel/Decel Time]
.
OFF : Enabled
Enables
b5-17 [PID Accel/Decel Time]
.
Note:
Refer to
“
PID control block diagram
”
for more information.
■
35: PID Input (Error) Invert
Setting Value
Function
Description
35
PID Input (Error) Invert
Sets the command to turn the terminal ON and OFF to switch the PID input level (polarity).
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...