YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
307
Note:
•
Setting range differs by protocol:
–
BACnet: 3, 4, 5, 7
–
P1: 2, 3
–
N2: 3
–
Modbus: 0 to 8
•
Re-energize the drive or set
H5-20 = 1 [Communication Parameters Reload = Reload Now]
after you change the parameter setting.
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
3 : 9600 bps
4 : 19.2 kbps
5 : 38.4 kbps
6 : 57.6 kbps
7 : 76.8 kbps
8 : 115.2 kbps
■
H5-03: Communication Parity Selection
No.
(Hex.)
Name
Description
Default
(Range)
H5-03
(0427)
Communication Parity
Selection
Sets the communications parity used for MEMOBUS/Modbus communications.
0
(0 - 2)
Note:
Re-energize the drive or set
H5-20 = 1 [Communication Parameters Reload = Reload Now]
after you change the parameter setting.
0 : No parity
1 : Even parity
2 : Odd parity
■
H5-04: Communication Error Stop Method
No.
(Hex.)
Name
Description
Default
(Range)
H5-04
(0428)
Communication Error Stop
Method
Sets the motor Stopping Method when the drive detects a Modbus Communication Error condition.
3
(0 - 4)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. Fault relay output terminal MA-MC activates and MB-MC
deactivates.
1 : Coast to Stop
The output turns off and the motor coasts to stop. Fault relay output terminal MA-MC turns activates and MB-MC
deactivates.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in
C1-09 [Fast Stop Time]
. Fault relay output terminal MA-MC
activates and MB-MC deactivates.
3 : Alarm Only
The keypad shows a
CE [Modbus Communication Error]
alarm and the drive continues operation. The output
terminal set for
Alarm [H2-01 to H2-03 = 10]
activates.
4 : Run at H5-34 (CE Go-To-Freq)
The keypad shows a
CE [Run at H5-34 (CE Go-To-Freq)]
alarm and the drive will operate at the speed set in
H5-34
[Comm Error (CE) Go-To-Frequency]
when a Communication Error condition occurs.
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...