5.10 o: Keypad-Related Settings
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
361
■
o1-47: Trend Plot 1 Scale Minimum Value
No.
(Hex.)
Name
Description
Default
(Range)
o1-47
(11C7)
RUN
Trend Plot 1 Scale Minimum
Value
Sets the horizontal axis minimum value used to display the monitor set in
o1-24 [Custom Monitor 1]
as a trend plot. This parameter is only available on an HOA keypad.
-100.0%
(-300.0 - +300.0%)
■
o1-48: Trend Plot 1 Scale Maximum Value
No.
(Hex.)
Name
Description
Default
(Range)
o1-48
(11C8)
RUN
Trend Plot 1 Scale
Maximum Value
Sets the horizontal axis maximum value used to display the monitor set in
o1-24 [Custom Monitor 1]
as a trend plot. This parameter is only available on an HOA keypad.
100.0%
(-300.0 - +300.0%)
■
o1-49: Trend Plot 2 Scale Minimum Value
No.
(Hex.)
Name
Description
Default
(Range)
o1-49
(11C9)
RUN
Trend Plot 2 Scale Minimum
Value
Sets the horizontal axis minimum value used to display the monitor set in
o1-25 [Custom Monitor 2]
as a trend plot. This parameter is only available on an HOA keypad.
-100.0%
(-300.0 - +300.0%)
■
o1-50: Trend Plot 2 Scale Maximum Value
No.
(Hex.)
Name
Description
Default
(Range)
o1-50
(11CA)
RUN
Trend Plot 2 Scale
Maximum Value
Sets the horizontal axis maximum value used to display the monitor set in
o1-25 [Custom Monitor 2]
as a trend plot. This parameter is only available on an HOA keypad.
100.0%
(-300.0 - +300.0%)
■
o1-51: Trend Plot Time Scale Setting
No.
(Hex.)
Name
Description
Default
(Range)
o1-51
(11CB)
RUN
Trend Plot Time Scale
Setting
Sets the time scale (horizontal axis) to display the trend plot. When you change this setting, the drive
automatically adjusts the data sampling time. This parameter is only available on an HOA keypad.
300 s
(1 - 3600 s)
■
o1-55: Analog Gauge Area Selection
No.
(Hex.)
Name
Description
Default
(Range)
o1-55
(11EE)
RUN
Analog Gauge Area
Selection
Sets the range used to display the monitor set in
o1-24 [Custom Monitor 1]
as an analog gauge. This
parameter is only available on an HOA keypad.
1
(0, 1)
0 : +/- Area ( - o1-56 ~ o1-56 )
1 : + Area ( 0 ~ o1-56 )
■
o1-56: Analog Gauge Area Setting
No.
(Hex.)
Name
Description
Default
(Range)
o1-56
(11EF)
RUN
Analog Gauge Area Setting
Sets the value used to display the monitor set in
o1-24 [Custom Monitor 1]
as an analog meter. This
parameter is only available on an HOA keypad.
100.0%
(0.0 - 100.0%)
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...