310
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
This parameter and
H5-15 [BACnet Device Obj ID HIGH BITS]
set the Instance Identifier of the BACnet Device
Object. The
H5-14
value is the least significant word and the
H5-15
value is the most significant word. Refer to these
examples to set
H5-14
and
H5-15
correctly:
•
Example 1: Set Device Object Instance Identifier of
“
1234
”
The number of 1234 (decimal) is equal to 4D2 (hexadecimal). Set
H5-14 = 04D2
and
H5-15 = 0000
.
•
Example 2: Set Device Object Instance Identifier of
“
1234567
”
The number of 1234567 (decimal) is equal to 12D687 (hexadecimal). Set
H5-14 = D687
and
H5-15 = 0012
.
■
H5-15: BACnet Device Obj ID HIGH BITS
No.
(Hex.)
Name
Description
Default
(Range)
H5-15
(310E)
BACnet Device Obj ID
HIGH BITS
Sets the upper bits of the BACnet device object ID as a 4-digit hexadecimal number.
0000
(0000 - 003F)
Parameter
H5-14 [BACnet Device Obj ID LOW BITS]
and this parameter set the Instance Identifier of the BACnet
Device Object. The
H5-14
value is the least significant word and the
H5-15
value is the most significant word. Refer
to these examples to set
H5-14
and
H5-15
correctly:
•
Example 1: Set Device Object Instance Identifier of
“
1234
”
The number of 1234 (decimal) is equal to 4D2 (hexadecimal). Set
H5-14 = 04D2
and
H5-15 = 0000
.
•
Example 2: Set Device Object Instance Identifier of
“
1234567
”
The number of 1234567 (decimal) is equal to 12D687 (hexadecimal). Set
H5-14 = D687
and
H5-15 = 0012
.
■
H5-18: Motor Speed Filter over Comms
No.
(Hex.)
Name
Description
Default
(Range)
H5-18
(11A2)
Motor Speed Filter over
Comms
Sets the filter time constant used when monitoring motor speed during MEMOBUS/Modbus
communications or with a communication option.
0 ms
(0 - 100 ms)
Sets the filter time constant when you monitor the output frequency or motor speed during MEMOBUS/Modbus
communications or use of the communication option.
These are the MEMOBUS registers:
•
003EH (Output Frequency)
•
003FH (Output Frequency)
•
0044H (
U1-05
: Motor Speed)
•
00ACH (
U1-05
: Motor Speed)
•
00ADH (
U1-05
: Motor Speed)
■
H5-20: Communication Parameters Reload
No.
(Hex.)
Name
Description
Default
(Range)
H5-20
(0B57)
Communication Parameters
Reload
Sets the function to immediately enable updated MEMOBUS/Modbus communications parameters.
0
(0, 1)
0 : Reload at Next Power Cycle
1 : Reload Now
Note:
•
The setting value automatically returns to
H5-20 = 0
after you enable MEMOBUS/Modbus communications parameter changes.
•
The setting values of these parameters are enabled:
–
H5-01 [Drive Node Address]
–
H5-02 [Communication Speed Selection]
–
H5-03 [Communication Parity Selection]
–
H5-06 [Drive Transmit Wait Time]
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...