23
Appendix
Network cable connections
332
Vanderbilt
Installation & Configuration Manual
A6V10276959
01.05.2016
23
Appendix
23.1
Network cable connections
A PC can be connected directly to the Ethernet interface of the SPC controller or
via a LAN connection. The tables below show the 2 possible connection
configurations.
If the SPC is connected to an existing network via a hub, then connect a
straight through cable from the hub to the SPC and another from the hub to the
PC.
If the controller is not connected to a network (i.e. a hub or switch is not used),
then a crossover cable should be connected between the SPC controller and
the PC.
Use the straight through cable for connecting the SPC controller to a PC via a hub.
RJ45 PIN
RJ45 PIN
1 (RX +)
1 (TX +)
2 (RX -)
2 (TX -)
3 (TX+)
3 (RX+)
6 (TX-)
6 (RX-)
Use the crossover cable for connecting the SPC controller directly to a PC.
RJ45 PIN
RJ45 PIN
1 (RX +)
3 (TX+)
2 (RX -)
6 (TX-)
3 (TX+)
1 (RX +)
6 (TX-)
2 (RX -)
23.2
Controller status LEDs
LED
Function
LED 1
Wireless Data
FLASHING: wireless data is being received by the wireless module
OFF: no wireless data is being received
LED 2
Battery Status
ON: battery voltage has dropped below the deep discharge level (10.9 V)
OFF: battery status OK
IP
Содержание SPCK620
Страница 1: ...A6V10276959 Vanderbilt 01 05 2016 SPC42xx 43xx 52xx 53xx 63xx Installation Configuration Manual 3 6 ...
Страница 364: ...23 Appendix ATP Category Timings 364 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 365: ...Appendix 23 ATP Category Timings 365 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 366: ...23 Appendix ATP Category Timings 366 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 367: ...Appendix 23 ATP Category Timings 367 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...