22
Blocking Lock Operation
Blocking Lock
328
Vanderbilt
Installation & Configuration Manual
A6V10276959
01.05.2016
22
Blocking Lock Operation
Blocking Lock operation and the Authorized Setting operation of a Blocking Lock is
supported by the SPC intrusion panel.
22.1
Blocking Lock
A Blocking Lock is a mechanical lock which is mounted into a door in addition to
the normal lock and is used to set and unset the intrusion system. SPC support
normal Blocking Lock devices (Blockschloss 1) and also the Bosch Blockschloss,
Sigmalock Plus, E4.03 device (Blockschloss 2).
Depending on the kind of Blocking Lock, a signal is needed to enable locking and
unlocking the lock i.e. the Blocking Lock can only be locked and the system set if
the signal Ready to Set is available from the control panel. This is controlled by a
magnetic switch.
The operation of a Blocking Lock is as follows:
1. If there is no open zone, pending alarm or pending fault in the area, the area is
ready to set and the Ready to Set signal is sent from the panel.
2. If the Blocking Lock device is then locked, the Blockschloss 1/2 output is
activated.
3. Following the corresponding change on the Keyarm input type, the respective
area is set.
4. The Setting Ack output is activated for 3 seconds to signal a successful setting
of the area. Blockschloss 1 output is deactivated when the system is set.
Blockschloss 2 stays activated when the system is set.
5. If the Blocking Lock is unlocked, the Keyarm input is switched to the unset
state (closed).
6. Following the change on the Keyarm input type, the area is unset. Blockschloss
1 is deactivated if the area is ready to set while Blockschloss 2 is activated if
the area is ready to set.
No open zone,
pending alarm or
pending fault
Ready to Set
Keyarm
Blocking
Device
Locked
Area Set
Blockschloss 1/2
Setting Ack
Fullset Done
Panel
Input
Output
Output
Output
Output
Blocking Lock
Setting Start
3 secs
Содержание SPCK620
Страница 1: ...A6V10276959 Vanderbilt 01 05 2016 SPC42xx 43xx 52xx 53xx 63xx Installation Configuration Manual 3 6 ...
Страница 364: ...23 Appendix ATP Category Timings 364 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 365: ...Appendix 23 ATP Category Timings 365 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 366: ...23 Appendix ATP Category Timings 366 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 367: ...Appendix 23 ATP Category Timings 367 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...