General Information
The DS9447 is a 4-wire Alpha-Numeric LCD keypad. It may
be surface mounted, mounted to standard single or double
gang boxes, or to 4 inch square boxes.
The following is a chart of general wiring guidelines:
Keypad Addresses
Important:
Each keypad must have its address set with its
address pins. The keypads must also be
programmed at the control panel.
• Select the keypad address (1-15).
Place the shorting jumpers over the address pins as
shown at the top of the next column.
Remember
: Each keypad must have its own address, and
each address can only support one device.
Mounting
The keypad should be mounted no higher than shoulder
height of the shortest person using the system.
• Remove the keypad’s cover.
Insert a small flat-head screwdriver in each slot at the
bottom of the base. Press up, and pull the cover off.
• Surface Mounting:
Use the base as a template and mark the location of the
mounting holes (use any holes).
Provide an opening in the mounting surface for the wiring.
Pre-start the mounting screws.
Do not secure the base at this point.
• Electrical Box Mounting:
See the diagram on page 2 to select the mounting holes.
Do not secure the base at this point.
Installation Instructions
for the
DS9447 Control Station / Keypad
Wire Gage
22 AWG (0.8 mm) minimum.
18 AWG (1 mm) is required for
NEC-NFPA-72.
Wire Type
non-shielded, 4-wire
Max number of
keypads allowed
per system
4
Max distance
allowed between
the control and
the keypad
1,000 feet (304.8 m)
Max distance of
keypad wiring
per system
4,000 feet (1219.2 m)
1
2
4
8
1
2
4
8
1
2
4
8
1
2
4
8
1
2
4
8
address 1
address 4
address 7
address 10
address 13
1
2
4
8
1
2
4
8
1
2
4
8
1
2
4
8
1
2
4
8
address 2
address 5
address 8
address 11
address 14
1
2
4
8
1
2
4
8
1
2
4
8
1
2
4
8
1
2
4
8
address 3
address 6
address 9
address 12
address 15
DS9447
Alarm
Silenced
Power
Trouble
1
2
3
4
5
6
7
8
9
0
Program
*
#
Command
Silence
Disable
History
Test
Drill
Reset
Clear