Engineer programming via the browser
17
Configuring Communications
297
Vanderbilt
Installation & Configuration Manual
A6V10276959
01.05.2016
Description
Edit the name of the EDP receiver. Maximum 16 characters.
Receiver ID
Edit the EDP receiver ID. Range is 1 to 999997 (999998 and
999999 are reserved for special purposes)
Protocol Version
Select the EDP protocol version to use with this EDP receiver.
Options are Version 1 or Version 2. Version 2 is recommended if
supported by the receiver, as it is a more secure protocol.
VdS 2471
Compatible
(Vds standard only)
If this option is selected then the EDP receiver will enforce the
following settings for that receiver:
8s polling interval
TCP protocol enforced
TCP retries will fail before 10s (9s approx)
EDP event retries are set to 1 independent of the global “Retry
Count” setting in “EDP Settings”
FTC will be generated within 20s of network failure.
Security