The configuration requirements for Authorised Setting are as follows:
Area Attributes:
– Setting Authorisation
Set
Set and Unset (required for VdS)
Unset
Outputs:
– Ready to set
– Setting Ack
– Fullset Done
Inputs
– Keyarm
22.3
Locking Element
For VdS, it is mandatory to prevent entering a set area. This is done by using a
Lock Element which is mounted in the doorframe. The lock element consists of a
small plastic bolt which locks the door in a SET state. The position of the bolt is
signaled by Lock element – Lock or Lock element – Unlock outputs. This signal is
checked during the setting process. If the “locked” information is not received, the
setting fails.
If a lock element is located within an area, the exit timer will be restricted to a
minimum of 4 seconds so that the lock element can be activated. When the exit
timer reaches four seconds, the lock element will be activated for three seconds.
When the exit timer expires, the Lock Element input must be in the closed state
then the system will set.
If a lock element is opened during a set period it will be handled as an alarm zone.
If a lock element is closed during an unset process then it will be considered to be
tampered and raise a tamper on the zone.
If the lock element fails to open after the unlock signal is sent to the device, then a
trouble will be raised on that zone to signal that a mechanical failure has occurred.
If the Lock Element input (if configured) is not in the closed state when the exit
timer expires, then the system will not set and a Fail to Set signal will be raised.
The Lock Element – Unlock output will be activated.
Содержание SPCK620
Страница 1: ...A6V10276959 Vanderbilt 01 05 2016 SPC42xx 43xx 52xx 53xx 63xx Installation Configuration Manual 3 6 ...
Страница 364: ...23 Appendix ATP Category Timings 364 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 365: ...Appendix 23 ATP Category Timings 365 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 366: ...23 Appendix ATP Category Timings 366 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 367: ...Appendix 23 ATP Category Timings 367 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...