10
Wiring the system
Wiring the X-BUS interface
72
Vanderbilt
Installation & Configuration Manual
A6V10276959
01.05.2016
10
Wiring the system
10.1
Wiring the X-BUS interface
The X-BUS interface provides for the connection of expanders to the controller.
The X-BUS can be wired in a number of different configurations depending on the
installation requirements. The X-BUS interface baud rate is 307 kb.
NOTICE
The X-BUS is an RS-485 bus with a baud rate of 307 kb. The full performance is
only supported in loop [➙ 73] and spur [➙ 74] wiring configuration (best signal
quality due to daisy chain of isolated sections with 1 transmitter / 1 receiver and
balanced terminating resistors on each end).
The performance in star [➙ 75] or multi-drop [➙ 75] configuration wiring is limited
due to non-optimal conditions of the RS-485 bus specification (reduced signal
quality due to multiple receivers / transmitters in parallel with unbalanced
terminating resistors).
NOTICE
It’s strongly recommended to use loop [➙ 73] or spur [➙ 74] configuration.
The table below shows the maximum distances between controller / expander or
expander / expander for all cable types in loop and spur configuration.
Cable Type
Distance
CQR standard alarm cable
200 m
UTP Category: 5 (solid core)
400 m
Belden 9829
400 m
IYSTY 2 x 2 x 0.6 (min)
400 m
Each device has 4 terminals (1A, 1B, 2A, 2B) for connection to expanders via the
X-BUS cable. The controller initiates a detection procedure on power up to
determine the number of expanders connected on the system and the topology in
which they are connected.
Содержание SPCK620
Страница 1: ...A6V10276959 Vanderbilt 01 05 2016 SPC42xx 43xx 52xx 53xx 63xx Installation Configuration Manual 3 6 ...
Страница 364: ...23 Appendix ATP Category Timings 364 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 365: ...Appendix 23 ATP Category Timings 365 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 366: ...23 Appendix ATP Category Timings 366 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 367: ...Appendix 23 ATP Category Timings 367 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...