Powering up the SPC controller
11
Powering from battery only
89
Vanderbilt
Installation & Configuration Manual
A6V10276959
01.05.2016
11
Powering up the SPC controller
The SPC controller has two power sources, the mains supply and the integral
standby battery. A qualified electrician should undertake connection to the mains
and the mains supply should be connected from a spur that can be isolated. See
Page [➙ 346] for full details of conductor sizes / fuse ratings etc.
The SPC should be powered from the mains first and then the internal standby
battery. For compliance to EN only one battery should be fitted of the appropriate
capacity.
11.1
Powering from battery only
It is recommended that when powering a system from battery only, the battery
should be in a fully charged state (>13.0 V). The system will not power up when
using a battery with less than 12 V and no mains is applied.
NOTICE
The battery will continue to power the system until deep discharge level (10.5 V to
10.8 V) has been detected. The time duration that the system will hold up on
battery will depend on the external loading and Ah rating of the battery.
Содержание SPCK620
Страница 1: ...A6V10276959 Vanderbilt 01 05 2016 SPC42xx 43xx 52xx 53xx 63xx Installation Configuration Manual 3 6 ...
Страница 364: ...23 Appendix ATP Category Timings 364 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 365: ...Appendix 23 ATP Category Timings 365 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 366: ...23 Appendix ATP Category Timings 366 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 367: ...Appendix 23 ATP Category Timings 367 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...