Refer to the following sections in this manual:
Timers [➙ 114]
Zone attributes [➙ 350]
OUTPUTS [➙ 136] (Keypad)
Editing an output [➙ 197] (Browser)
Intrusion and confirmed hold-up alarm (BS8243:2010 Designation of
hold-up alarm (HUA) signals for sequential confirmation)
SPC system is configurable in such a way that the following scenarios, when
triggered more than two minutes apart from any hold-up zone or hold-up device
(HD), will report a confirmed hold-up alarm event (HV for SIA and 129 for CID) to
the CIE:
two hold-up zone activations
a hold-up zone and a panic zone activation
If a hold-up zone and a tamper zone or a panic zone and a tamper zone activation
occurs within the two minute period, this will also send a confirmed hold-up alarm
event.
A confirmed hold-up will not require an engineer restore even if engineer restore is
enabled. A confirmed hold-up event is logged in the system log.
Security of communications for remote support and remote system
checks (DD 263:2010)
Please ensure that SPC Pro is used within the guidelines specified in DD
263:2010.
3.1.5.5
Additional commissioning requirements for PD 6662:2010
conformance
Information to be included in the system design proposal and as-
fitted document (BS 8243:2010 - Annex F)
During the installation, configuration and commissioning of an SPC system, the
installer must adhere to the following guidelines as required in the above
annex:
It is recommended that dual paths are used for signalling which are supported
in the SPC system using GSM, PSTN and Ethernet options.
The SPC system must be installed and configured to provide an effective
confirmation facility. Any exceptions to this should be outlined in the ‘As Fitted’
document.
Combinations and sequences which contribute to a confirmed alarm should be
clearly notified to the end user.
The intrusion confirmation time should be clearly notified to the end user.
Methods of completion of setting and unsetting methods should be clearly
described to the end user as detailed in this document.
Ensure written arrangements are supplied to the end user in the event of a lock
failure.
Содержание SPCK620
Страница 1: ...A6V10276959 Vanderbilt 01 05 2016 SPC42xx 43xx 52xx 53xx 63xx Installation Configuration Manual 3 6 ...
Страница 364: ...23 Appendix ATP Category Timings 364 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 365: ...Appendix 23 ATP Category Timings 365 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 366: ...23 Appendix ATP Category Timings 366 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 367: ...Appendix 23 ATP Category Timings 367 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...