3
Directives and standards
EU directives
22
Vanderbilt
Installation & Configuration Manual
A6V10276959
01.05.2016
Selecting Grade 2 or Grade 3 selects EN50131 compliance plus any additional
INCERT requirements:
Only an engineer can restore a tamper. For INCERT, this applies across all
grades.
This is normally only a requirement for Grade III En50131.
A tamper on an Inhibited / Isolated zone must be sent to an ARC and displayed
to the user.
For INCERT, tampers are processed for isolated zones. On all other standard
variations, tampers are ignored on isolated zones.
User PIN codes must be defined with more than 4 digits.
Hardware Requirements
The minimum battery capacity for SPC42xx/43xx/52xx/53xx/63xx is 10 Ah / 12
V. If a 10 Ah battery is used, then the battery is biased to the left of the cabinet
and the bottom flap is bent to meet the battery.
Fit jumper (J12) on the battery selector for 17/10 Ah battery use and remove for
7 Ah battery.
The amount of current from Aux output using a 10 Ah battery for
SPC42xx/SPC52xx is:
COMMS
NONE
PSTN
GSM
PSTN+GSM
Standby time
12 h
568 mA
543 mA
438 mA
413 mA
24h
214 mA
189 mA
84 mA
59 mA
30 h
143 mA
118 mA
13 mA
N/A
60h
2mA
N/A
N/A
N/A
Содержание SPCK620
Страница 1: ...A6V10276959 Vanderbilt 01 05 2016 SPC42xx 43xx 52xx 53xx 63xx Installation Configuration Manual 3 6 ...
Страница 364: ...23 Appendix ATP Category Timings 364 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 365: ...Appendix 23 ATP Category Timings 365 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 366: ...23 Appendix ATP Category Timings 366 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 367: ...Appendix 23 ATP Category Timings 367 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...