Engineer programming via the browser
Configuration
244
Vanderbilt
Installation & Configuration Manual
A6V10276959
01.05.2016
automatically. (Range 0 – 120 mins: 0 = not
active).
Dual PIN
If this option is enabled, two PINs are
required to Set or Unset the area with the
keypad. Both PINs must belong to users
who have the required user right for the
operation (Setting or Unsetting).
If the second PIN is not entered within 30
seconds, or it is wrong, then the area cannot
be Set or Unset.
Late Working Support
An example of using the setting and unsetting parameters is for late working
situations where a calendar has been configured for automatic setting of a
premises at a particular time but staff may need to work late on occasion and the
automatic setting needs to be delayed.
Each delay is determined by the amount configured in the Delay Interval
parameter, and the Delay Counter parameter determines the number of times that
setting can be delayed. A user needs the correct value in the Auto Set Delay in
order to use this feature.
There are three ways to delay setting:
1. Entering the PIN on the keypad.
DELAY is a menu option on the standard keypad. The buttons at the top of the
comfort keypad are used to operate the delay feature
2. Using the keyswitch.
Turning the key to the right delays setting the system by the configured delay if
the maximum number of times that setting can be delayed (Delay Counter) has
not been exceeded. Turning the key to the left sets the delay to three minutes
(non-configurable). This can be done regardless of how many times setting
was delayed.
3. Using a FOB, WPA or button which activates a Delay Autoset trigger action.
(See page 172)
Temporary Unset
To allow a system to be temporarily unset in a time period specified by a calendar,
the following three parameters need to be configured:
1. Calendar
A calendar needs to be configured and selected for this area.
2. Time Locked
This box needs to be ticked so that the area can be unset only when allowed
as per the configured calendar.
3. Unset Duration
This parameter needs to be set to a value greater than zero to set an upper
limit on the time the area will be unset.
The following screen shows these parameters configured with appropriate settings:
All Okay
All Okay Required
If selected, user must confirm ‘All okay’ input or silent alarm is
generated. See Editing a Zone [➙ 237] for details on configuring an ‘All
Okay’ zone input.
17.9.5.2.7
Содержание SPCK620
Страница 1: ...A6V10276959 Vanderbilt 01 05 2016 SPC42xx 43xx 52xx 53xx 63xx Installation Configuration Manual 3 6 ...
Страница 364: ...23 Appendix ATP Category Timings 364 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 365: ...Appendix 23 ATP Category Timings 365 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 366: ...23 Appendix ATP Category Timings 366 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 367: ...Appendix 23 ATP Category Timings 367 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...