18
Accessing web server remotely
GSM connection
318
Vanderbilt
Installation & Configuration Manual
A6V10276959
01.05.2016
The web server on the controller can be accessed via a remote connection over
the GSM network. A GSM module (with SIM card) must be installed on the
controller as shown above to provide remote access to the SPC. The data option of
the SIM card must be activated and the data number must be used.
On the remote side of the connection the user must have a PSTN or GSM modem
installed on a PC with browser. If a PSTN modem is installed then it must be
connected to a working PSTN line.
To connect remotely to the controller:
1. Install a GSM modem on the controller (please refer to corresponding
installation instruction).
2. Enter Full Engineer programming from the keypad and configure the modem
(primary or backup) to answer an incoming call.
3. On the keypad, scroll to the following menu: FULL ENGINEER >
COMMUNICATION > MODEMS, and select the settings listed:
Enable Modem
Set to Modem Enabled.
Type
Displays the type of modem (GSM).
Country Code
Select the relevant country code.
Answer Mode
Select numbered rings; this tells the modem to wait for a number of rings before
answering the incoming call.
Modem Rings
Select the number of rings to allow before answering the call (8 rings max).
On Windows XP:
1. Open the New Connection Wizard by browsing to Control Panel > Network
Connections > Create New Connection (in the Network Tasks window).
2. In the Network Connection Type window, select Connect to the Internet.
3. In the Getting Ready window, choose Setup my connection manually.
4. In the Internet Connection window, choose Connect using Dialup modem.
5. In the Connection Name window enter the connection name e.g. SPC remote
connection.
6. In the Phone Number to Dial window, enter the phone number of the PSTN line
connected to the PSTN modem.
7. In the Connection Availability window, choose whether this connection is
available to all users.
8. In the Internet Account Information window, enter the following details:
- Username : SPC
- Password: password (default)
- Confirm Password: Vanderbilt
The Completing the New Connection Wizard window is displayed.
9. Click Finish to save the Dial-up connection to the PC.
Default code should be changed and noted accordingly as Vanderbilt
is unable to retrieve this new code. Forgotten codes are be remedied only by a
factory default of the system, rendering loss of programming. Programming can
be restored if a backup is available.
Содержание SPCK620
Страница 1: ...A6V10276959 Vanderbilt 01 05 2016 SPC42xx 43xx 52xx 53xx 63xx Installation Configuration Manual 3 6 ...
Страница 364: ...23 Appendix ATP Category Timings 364 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 365: ...Appendix 23 ATP Category Timings 365 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 366: ...23 Appendix ATP Category Timings 366 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 367: ...Appendix 23 ATP Category Timings 367 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...