Engineer programming via the keypad
16
X-BUS
119
Vanderbilt
Installation & Configuration Manual
A6V10276959
01.05.2016
To refresh the X-Bus status:
1. Scroll to XBUS REFRESH.
2. Press SELECT.
The number of online keypads is displayed.
3. Press the right soft key on the keypad after each display to view expanders,
zones and offline items.
4. Press this key again to exit.
Refresh makes no changes to the system, but is useful for detecting system
faults, such as loose connections, or inactive expanders, before performing a
Reconfigure.
16.6.3
Reconfigure
NOTICE
A reconfigure only applies to wired zones on an expander. Wireless zones on an
expander and controller zones will not be brought online after a reconfigure. To
bring controller zones online, you must apply a zone type other than ‘Unused’
using the zones menu on the keypad or web browser.
If the system has a mixture of expander types (with and without rotary switches)
then the system can only be automatically reconfigured. If the system has all
expanders with rotary switches, the system can still be automatically reconfigured
and the system will ignore the rotary switches and auto addresses all the
expanders on the system.
It is recommended that you perform a Refresh before a Reconfigure.
To reconfigure keypads/expanders:
1. Scroll to RECONFIGURE.
2. Press SELECT.
The number of online keypads is displayed.
3. Press NEXT.
The number of online expanders is displayed.
4. Press NEXT
The number of online zones is displayed.
5. Press BACK to exit.
Содержание SPCK620
Страница 1: ...A6V10276959 Vanderbilt 01 05 2016 SPC42xx 43xx 52xx 53xx 63xx Installation Configuration Manual 3 6 ...
Страница 364: ...23 Appendix ATP Category Timings 364 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 365: ...Appendix 23 ATP Category Timings 365 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 366: ...23 Appendix ATP Category Timings 366 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 367: ...Appendix 23 ATP Category Timings 367 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...