16
Engineer programming via the keypad
Test
146
Vanderbilt
Installation & Configuration Manual
A6V10276959
01.05.2016
2. Press SELECT.
3. Scroll to a preferred zone and press SELECT.
The status of the zone and its associated resistance value is displayed.
4. Press NEXT to locate the zone (e.g. CONTROLLER 1 = first zone on
Controller).
Refer to the table below for correlating status information (valid for Dual EOL
resistors).
Zone status
Abbreviation
UNKNOWN
UK
CLOSED
CL
OPEN
OP
SHORT
SH
DISCONNECTED
DI
PULSE
PU
GROSS
GR
MASKED
AM
FAULT
FA
DC SUB
DC
OUT OF BOUNDS
OB
UNSTABLE
US
All zones on a system can be monitored for correct operation by performing a
monitoring test.
To perform a zone monitoring test:
1. Scroll to ZONE MONITOR.
2. Press SELECT.
3. Scroll to a preferred zone and press SELECT, or enter the zone number
directly.
If the zone is located close to the keypad, the status of the keypad can be
viewed as it changes. The Zone status and resistance value displays on
the top right.
4. Change the state of the sensor; e.g. for a door contact sensor, open the door.
The keypad buzzer beeps and the status of the sensor changes from CL
(Closed) to OP (Open). The corresponding resistance value changes to a value
that depends on the EOL resistance scheme.
It is advisable to check the operation of all zones on the system after installation
is complete. To locate the zone select NEXT (bottom right) on the keypad. A zone
status value of SH or DI indicates that the zone is shorted or disconnected.
16.12.4
Output Test
To perform an output test:
1. Scroll to OUTPUT TEST.
2. Press SELECT.
3. Toggle between CONTROLLER and EXPANDER for preferred option.
Содержание SPCK620
Страница 1: ...A6V10276959 Vanderbilt 01 05 2016 SPC42xx 43xx 52xx 53xx 63xx Installation Configuration Manual 3 6 ...
Страница 364: ...23 Appendix ATP Category Timings 364 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 365: ...Appendix 23 ATP Category Timings 365 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 366: ...23 Appendix ATP Category Timings 366 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 367: ...Appendix 23 ATP Category Timings 367 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...