10
Wiring the system
Wiring the X-BUS interface
80
Vanderbilt
Installation & Configuration Manual
A6V10276959
01.05.2016
Not allowed wiring with a second star point
NOTICE
If the mix of star and multi-drop configuration is not properly wired the reduced
signal quality may lead to slow reaction time of connected devices (e.g. keypad
operation) or even loss of communication to devices. If such behavior is observed
a wiring in loop OR star configuration is strongly recommended.
10.1.4
Shielding
The shielding terminals (SHLD) should only be used for cables types with
shielding (e.g. Belden 9829). If shielding is required (i.e. sites with high electric
field interference): connect the cable shield to the SHLD terminals on the
controller and all networked expanders. If the shield needs to be connected to
earth then a cable needs to be connected from the SHLD terminal on the
controller to the chassis earth stud. Do NOT earth the SHLD terminal on any of
the expanders.
NOTICE
For star and multi-drop wiring
It’s not recommended to use shielded cables due to disadvantageous electrical
characteristics (higher capacitance) in star and multi-drop wiring configuration.
However, if shielding is required (i.e. sites with high electric field interference) a
new wiring in proper spur or loop configuration with appropriate installation cable
configuration has to be done.
Содержание SPCK620
Страница 1: ...A6V10276959 Vanderbilt 01 05 2016 SPC42xx 43xx 52xx 53xx 63xx Installation Configuration Manual 3 6 ...
Страница 364: ...23 Appendix ATP Category Timings 364 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 365: ...Appendix 23 ATP Category Timings 365 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 366: ...23 Appendix ATP Category Timings 366 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 367: ...Appendix 23 ATP Category Timings 367 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...