Engineer programming via the browser
Configuration
226
Vanderbilt
Installation & Configuration Manual
A6V10276959
01.05.2016
Restriction System Option
Description
closed, a manual restore operation on the
keypad/browser is not required. If disabled it prevents the
user from restoring alerts by resetting the input that
triggered the alert.
Alarm on Exit
Enabled: If a non-entry/exit zone is activated during the
exit timer countdown, a local alarm is raised by sounding
the bells.
Disabled: If a non-entry/exit zone is activated during the
exit timer countdown, an alarm is not raised.
Note: This option only displays when the Unrestricted
grade is selected as enabling it is not in accordance with
EN50131. When you choose the Swiss or Belgium
Region under Standard Compliance Settings, this option
is automatically enabled but it is not visible under
Options.
Alarm on Entry
Enabled: If a non-entry/exit zone is activated during the
entry timer countdown, a local alarm is raised by
sounding the bells.
Disabled: If a non-entry/exit zone is activated during the
entry timer countdown, an alarm is not raised.
Note: This option only displays when the Unrestricted
grade is selected as enabling it is not in accordance with
EN50131. When you choose the Swiss Region under
Standard Compliance Settings, this option is
automatically enabled but it is not visible under Options.
Confirmation
Confirmation
The Confirmation variable determines when an alarm is
deemed to be a confirmed alarm.
BS8243:
This will enforce compliance with the UK Police
requirements, and is a specific requirement for UK
Commercial installations. The requirement stipulates
that an alarm will only be deemed to be a confirmed
alarm if it meets the following condition:
After an initial zone alarm has been activated and
before the alarm confirmation time has expired, a
second zone alarm is activated. The alarm
confirmation time must be between 30 and 60
minutes. (See Timers [➙ 230])
If a second zone alarm is not activated within the
Alarm confirmation time, then the first zone alarm will
be inhibited. The BS8243 confirmation option is
automatically set whenever the Standards -> Region
option is set to UK.
Garda:
This will enforce the policies for confirmed alarms
required by the Irish Garda. The requirement
stipulates that an alarm will be deemed to be a
confirmed alarm as soon as a second zone alarm is
activated on the system within the one alarm set
period. The Garda confirmation option is
automatically set whenever the Standards -> Region
option is set to Ireland.
EN-50131-9
This will enforce compliance with the EN-50131-9
standard and the Spanish “INT/316/2011 Order of 1
February on the operation of alarm systems in the
field of private security”. This requirement stipulates
that an alarm will only be deemed to be a confirmed
alarm if it meets the following conditions:
- 3 zone activations in 30 minutes (default), whereby
!
!
!
Содержание SPCK620
Страница 1: ...A6V10276959 Vanderbilt 01 05 2016 SPC42xx 43xx 52xx 53xx 63xx Installation Configuration Manual 3 6 ...
Страница 364: ...23 Appendix ATP Category Timings 364 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 365: ...Appendix 23 ATP Category Timings 365 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 366: ...23 Appendix ATP Category Timings 366 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 367: ...Appendix 23 ATP Category Timings 367 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...