background image

Page 1 of 8

2916P Proximity Keypad

Installation Instructions

I-EA00130

Rev 6, Rev Date: 5/29/19

Always visit www.hagerco.com for the latest Installation Instructions

HAGER COMPANIES 139 Victor Street, St. Louis, MO 63104 • (800) 325-9995

The 

2916P Keypad

 Indoor/Outdoor Keypad is a surface-mount digital 

keyless entry system designed for access control applications.  The backlit 
keys  are bright and easy-to-read. A heavy cast vandal resistant housing 
design with mounting plate allows the 2916P  to be mounted on a  rugged 
surface or on a standard single-gang electrical box.  
  
The 2916P has a capacity of 500 users. Users can be assigned to use 4 to 
6 digit  PIN codes and/or HID 125kHz proximity access credentials. An 
authenticated access can be programmed to activate one or both of the 
relay outputs. 

The timed 

anti-passback

” 

feature prevents using the same credentials  

twice  before a programmed waiting period has  elapsed.

Two long lasting solid state LED indicators show the status of the system.  
The left bi-color indicator lights red to indicate power, then green when a 
relay is active (access grant, etc.).  The right indicator flashes yellow to 
indicate that the keypad is in programming mode.

An internal sounder can be programmed to beep each time a key is 
pressed or when an output is activated.  An internal jumper sets the 
sounder volume high or low.

The 

SENSE 

input can be configured  two ways through programming .  

When configured for 

Door Sense

”, 

the input is wired to a normally closed 

door position switch to detect when the door is opened or closed.  Forced 
entry or door ajar situations can then be detected. The 

Auto-relock

” 

feature 

can also be used  to  turn off the Main Relay output immediately when the 
door is closed after access has been granted to prevent 

tailgating

”.

When the 

SENSE 

input is configured for 

Inhibit

”, 

the input can be wired to 

a normally open 

service

” 

switch or automatic timer that will disable access 

while the switch is closed.

The 

REQUEST-TO-EXIT 

input can be wired to a normally open pushbutton 

to provide codeless activation of the Main Relay, Auxiliary Relay, Output #3 
or Output #4 (programmable).

The 

ALARM SHUNT 

signal is available when access is granted.  This 

signal can be programmed to activate any of the relays or solid state 
outputs  to shunt alarm contacts on the access door/gate  preventing the  
triggering of an alarm when an authorized access occurs.

The 2916P is powered from a 12 or 24V AC or DC source. The non-volatile 
EEPROM memory retains  entry codes and programming when power is 
removed.  An internal jumper is provided to reset the master code.  The 
Main Relay has a 5 Amp capacity.  The Auxiliary Relay has a 2 Amp 
capacity.  Two solid state outputs, capable of sinking 100 mA to common 
are programmable for alarm shunting, or to signal forced entry, door ajar, 
keypad lockout, request-to-exit, and keypad active conditions.

INSTALLATION INSTRUCTIONS

2916P Keypad

SPECIFICATIONS

Mechanical

Dimensions:  3.00" W x 5.75" H x 1.375" D

      (1.4375” 

wall projection)

Electrical

Input Voltage: 12/24 Volts AC or DC
Operating Current: 30 mA typical, 150 mA max

  Output Ratings

   Main Relay: Form 

C

” 5 

Amps @ 28 Volts max

     Auxiliary Relay: Form 

C

” 2 

Amp @ 28 Volts max

Type:  Solid state outputs (Outputs #3 & #4)
Short-to-common 100 mA @ 24 VDC maximum

Environmental

Temperature: -4°F to 140°F (-20°C to 60°C)
Humidity: 5% to 95% non-condensing

Features

• 

4 to 6 digit user codes

• 

4 independent outputs

• 

4 independent timers

• 

2 Form C relay contacts

• 

2 solid state open collector outputs

• 

Program entry codes to activate one or 
two relays

• 

Disable input

• 

Door sense input

• 

Request-to-exit/Reception input

• 

Keypad tamper lockout

• 

Timed anti-passback

• 

Anti-tailgate

• 

Two LED status indicators

• 

Tactile key feel

• 

Audible code entry verification

• 

12V or 24V, AC or DC operation

                                                                

• 

Keypad programmable

• 

500 user codes

• 

3 User Modes 

PIN or Card
Card Only
Card and PIN

Содержание 2916P

Страница 1: ...nhibit the input can be wired to a normally open service switch or automatic timer that will disable access while the switch is closed The REQUEST TO EXIT input can be wired to a normally open pushbut...

Страница 2: ...ust first enter programming mode to perform any function The yellow indicator will blink slowly showing that the 2916P is in programming mode Use the option codes to program each function After the ne...

Страница 3: ...4 TRIGGERS A NORMALLY OPEN ALARM PANEL ZONE EXAMPLE 2 BLUE PINK SALMON OUTPUT 3 COM OUTPUT 4 COM POWER SOURCE OUTPUT 3 END OF LINE RESISTOR ALARM PANEL NO ZONE COMMON LOW VOLTAGE LAMP BLACK BLACK OUT...

Страница 4: ...Relay 2 Auxiliary Relay 3 Both Relays 10 Relay 1 toggled 20 Relay 2 toggled 30 both Relays toggled 12 Relay 1 toggled Relay 2 timed open 21 Relay 1 timed open Relay 2 toggled The yellow indicator will...

Страница 5: ...4 1 Main Relay 2 Auxiliary Relay 3 Output 3 4 Output 4 0 No Output Lockout Disable Select Alarm Shunt Output Default No Output Sets which output activates during the time access is granted Use this ou...

Страница 6: ...Sounds During Main Relay Default No Selects whether or not the keypad beeps during Main Relay activation Press 41 Sound Sound 1 for Yes 0 for No Solid state Output 4 On time Default 02 Seconds Sets t...

Страница 7: ...Always visit www hagerco com for the latest Installation Instructions HAGER COMPANIES 139 Victor Street St Louis MO 63104 800 325 9995 5 750 1 375 3 000 MOUNTING TO SINGLE GANG RECESSED OUTLET BOX 2X...

Страница 8: ...Rev 6 Rev Date 5 29 19 Always visit www hagerco com for the latest Installation Instructions HAGER COMPANIES 139 Victor Street St Louis MO 63104 800 325 9995 OPTIONAL SHROUD SURFACE MOUNT WITH OPTION...

Отзывы: