Page 5 of 8
2916P Proximity Keypad
Installation Instructions
I-EA00130
Rev 6, Rev Date: 5/29/19
Always visit www.hagerco.com for the latest Installation Instructions
HAGER COMPANIES 139 Victor Street, St. Louis, MO 63104 • (800) 325-9995
Configure Sense Input Default: INHIBIT
The Sense Input (gray wire) can be programmed for either
DOOR SENSE or INHIBIT.
Press: 10 # Input #
Input=0 for Door Sense; =1 for Inhibit
When programmed for DOOR SENSE, if an open condition on
the input occurs before access is granted (with an entry code or
with the request-to-enter input) a FORCED ENTRY output will
occur. If an open condition remains 60 seconds after a relay
activation for access, a DOOR AJAR output will occur.
When programmed for INHIBIT, a closed condition on the input
will prevent Relay #1 from activating when access is requested
with an entry code. This mode is typically used with an external
timer to disable the access device at certain times.
Select Forced Entry Output
Default: No Output
Sets which output activates if the DOOR SENSE input opens
before access is granted. This output is timed and configured
by the relay
“
On-time
”.
Press: 11 # Output #
Output=Output to Activate(0-4)
1=Main Relay; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
0=No Output
Select Door Ajar Output
Default: No Output
Sets which output activates if the DOOR SENSE input stays open
60 seconds after access is granted (door ajar time is adjustable
using Function 25). This output is not timed.
Press: 12 # Output #
Output=Output to Activate (0-4)
1=Main Relay; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
0=No Output
Select Keypad Active Output
Default: No Output
Sets which output activates when any keys are pressed. This
output is timed. If toggle mode is selected for the output, the timer
value defaults to 2 seconds.
Press: 14 #
Output
#
Output=Output to Activate(0-4)
1=Main Relay; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
0=No Output
Select Keypad Lockout Output
Default: No Output
Sets which output activates when the keypad is
“
locked out
”
after
too many incorrect entry code attempts. The lockout time is 60
seconds.
Press: 13
#
Output
#
Output=Output to Activate (0-4)
1=Main Relay; 2 = Auxiliary Relay; 3=Output #3; 4=Output #4;
0=No Output / Lockout Disable
Select Alarm Shunt Output
Default: No Output
Sets which output activates during the time access is granted.
(Use this output ot shunt alarm contacts attached to the access
door.) This output may be timed or toggled.
Press: 15 #
Output
#
Output=Output to Activate(0-4)
1=Main Relay; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
0=No Output
Select Request-to-Exit Output
Default: No Output
Sets which output activates when the Request-to-Exit input is
grounded. This output may be timed or toggled.
Press: 16 #
Output
#
Output=Output to Activate(0-4)
1=Main Relay; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
0=No Output
REX input terminates toggle of Main or Aux. Relay
Main Relay On-time
Default: 02 Seconds
Sets the length of time the Main Relay activates when triggered.
Green LED is on when Main Relay is active.
Press: 21 #
Seconds
#
Seconds=Output time in seconds (1-60)
Anti-Tamper Output
Default: No Output
Sets which output activates when the Anti Tamper switch on the
back of the keypad is activated.
Press: 17 #
Output
#
Output=Output to Activate(0-4)
0=No Output; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
Erasing All Entry Codes
WARNING: PERFORMING THIS COMMAND WILL REMOVE
ALL ENTRY CODES FROM THE MEMORY
Press: 97 # 0 0 0 0 0 0
# 0 0 0 0 0 0
#
Note:
The green indicator will light while the memory is being
erased. This may take up to 15 seconds.
Erasing Multiple Users (Sequential)
Press: 09 # 1
st
User
# Number of users
#
1
st
User =Starting user number to delete
Number of users = Total number of consecutive users to delete
The yellow indicator will flash quickly while the 2916P erases the
user from memory. The green indicator will light when the code
is erased.
Erasing a Single User
Press: 02 #
User
#
User
#
User =The user number to delete 001-500
The yellow indicator will flash quickly while the 2916P erases the
user from memory. The green indicator will light when the code is
erased.
Changing a User PIN
Press: 04 #
User
# New Code
# New Code
#
User =The user number whose PIN will be changed
See the following example that sets entry codes 1234 for normal
operation and 5678 for toggle operation.
Press: 01 # User # 1 2 3 4 # 1 2 3 4 # 1 #
01=Programming Step; 1234=Entry Code; 1=Main Relay
Press: 01 # User # 5 6 7 8 # 5 6 7 8 # 20 #
01=Program Step; 5678=Entry Code; 20=Auxiliary Relay toggle