E6582175
M-4
13
[Trip information]
Error code
Failure code
Name
Description
Remedies
*
001D
Low-current
operation
fault
The output current decreased to a low-
current detection level during operation.
Enable
(low-current detection).
Check the suitable detection level for the
system (
,
,
).
Contact your Toshiba distributor if the
setting is correct.
*
001E
Undervoltage fault
(main circuit)
The input voltage (in the main circuit) is
too low.
Check the input voltage.
Enable
(undervoltage trip
selection).
To take measures to momentary power
failure, set
=
, Regenerative
power ride-through control
f302
and
Auto-restart control selection
f301
.
0028
0054
0055
0056
Auto-tuning error
The motor parameter
,
,
,
,
are not set correctly.
Set the left column parameters correctly
as a motor name plate and make an auto-
tuning again.
Set parameter
f416
to smaller 70% of
the present value, and execute the auto-
tuning again.
The motor with the capacity of 2 classes
or less than the inverter is used.
The output cable is too thin.
The inverter is used for loads other than
those of three-phase induction motors.
Set the left column parameters correctly
as a motor name plate and make an auto-
tuning again.
Then set
f400
=
1
, when trip occurs.
The motor is not connected.
Connect the motor.
Check whether the secondary magnetic
contactor.
The motor is rotating.
Make an auto-tuning again after the
rotation of the motor stops.
Parameter
pt
=
6
is set and High speed
motor is connected.
Choose the higher power range drive.
(1 class up drive is recommended.)
0022
Ground fault
A ground fault occurs in the output cable
or the motor.
A ground fault occurs in dynamic braking
resistor.
Check the cable and the motor for ground
faults.
When inverters are fed by AC power
supply and connected with common DC
bus link, unnecessary trip occurs.
Set the parameter
f614
to
0
“Disabled”.
*
002F
Step-out (for PM
motor drive only)
The motor shaft is locked.
One output phase is open.
An impact load is applied.
Using the DC braking function.
Unlock the motor shaft.
Check the interconnect cables between
the inverter and the motor.
Prolong the acceleration / deceleration
time.
Turn off the Step-out function when using
the DC braking function or change the DC
braking to Servo lock function.
003B
Safe torque off error
Error of safe torque off circuit
Contact your Toshiba distributor.
0029
Inverter type error
It may be a breakdown failure.
Contact your Toshiba distributor.
002D
Over speed fault
The input voltage fluctuates abnormally.
Over speed fault due to the overvoltage
limit operation.
Check the input voltage.
Install an optional dynamic braking
resistor. (optional)
*
0032
Analog input break
detection fault
The input signal from VIC is equal to or
less than the
setting.
Check the VIC signal cable for breaks.
Also, check the input signal value or
setting of
.
0033
CPU communications
error
A communications error occurs between
control CPUs.
Contact your Toshiba distributor.
* This marking trips can be selected valid or invalid by parameters.