(1) Input withstand rating is that for which the product has been designed thermally.
(2) Output interrupt rating relies on Integral solid state short circuit protection. This does not provide branch circuit
protection. Branch circuit protection must be provided in accordance with the National Electrical Code and any
additional local codes. This is dependant on the type of installation.
In case of using with a higher AIC capability up to 100kA(*1), the Short Circuit Current Ratings (SCCR) become 100kA(*1)
by installing with the circuit breakers(GV3P) or the fuses listed in Table 4.
Table 4 AIC 100kA, Fuses, Circuit breakers and Wire sizes
Inverter model
Voltage
(V)
Branch circuit protection
Cable sizes of
power circuit
Earth Cable
With Fuses
With circuit breakers
Class (*2)
Rating
(A)
Type-Form
(*3)
Setting
(A)
VFS15-2004PM-W1
240
Class J
10
GV3P13
9
AWG 14
AWG 14
VFS15-2007PM-W1
240
Class J
15
GV3P13
9
AWG 14
AWG 14
VFS15-2015PM-W1
240
Class J
25
GV3P13
10
AWG 14
AWG 14
VFS15-2022PM-W1
240
Class J
25
GV3P18
18
AWG 12
AWG 14
VFS15-2037PM-W1
240
Class J
45
GV3P25
25
AWG 10
AWG 10
VFS15-2055PM-W1
240
Class J
60
GV3P40
40
AWG 8
AWG 10
VFS15-2075PM-W1
240
Class J
70
GV3P50
50
AWG 6
AWG 10
VFS15-2110PM-W1
240
Class J
100
GV3P65
65
AWG 6*2
AWG 8
VFS15-2150PM-W1
240
Class J
110
AWG 6*2
AWG 8
VFS15S-2002PL-W1
240
Class J
10
GV3P13
9
AWG 14
AWG 14
VFS15S-2004PL-W1
240
Class J
15
GV3P13
9
AWG 14
AWG 14
VFS15S-2007PL-W1
240
Class J
25
GV3P13
13
AWG 14
AWG 14
VFS15S-2015PL-W1
240
Class J
40
GV3P25
25
AWG 10
AWG 12
VFS15S-2022PL-W1
240
Class J
45
GV3P32
32
AWG 10
AWG 10
VFS15-4004PL-W1
480
Class J
6
GV3P13
9
AWG 14
AWG 14
VFS15-4007PL-W1
480
Class J
6
GV3P13
9
AWG 14
AWG 14
VFS15-4015PL-W1
480
Class J
15
GV3P13
9
AWG 14
AWG 14
VFS15-4022PL-W1
480
Class J
15
GV3P13
10
AWG 14
AWG 14
VFS15-4037PL-W1
480
Class J
25
GV3P13
13
AWG 12
AWG 14
VFS15-4055PL-W1
480
Class J
40
GV3P18
18
AWG 10
AWG 10
VFS15-4075PL-W1
480
Class J
40
GV3P25
25
AWG 8
AWG 10
VFS15-4110PL-W1
480
Class J
60
GV3P32
32
AWG 8
AWG 10
VFS15-4150PL-W1
480
Class J
70
GV3P40 (*1)
40
AWG 6
AWG 10
(*1) In case VFS15-4150PL with the circuit breaker, the Short Circuit Current Ratings (SCCR) is 65kA.
(*2) The manufacturer of the fuses should be "Cooper Bussmann" or "Mersen" (formerly, "Ferraz Shawmut") for the
compliance of UL standard.
(*3) The manufacturer of the listed circuit breaker is "Schneider Electric".